Parameter Information
B-7
Under-
voltage
Undervolt A Lvl
57
%V
0…99
0
Allows the user to set a voltage (% of line
Voltage) that will cause an Alarm when the
voltage falls below this value. A zero value is
the “off” setting.
Under-
voltage
Undervolt A Dly
58
Secs
0…99
0
Allows the user the ability to prevent some
nuisance Alarms by entering a delay period
that provides a window that the voltage
condition must persist within for the controller
to Alarm.
Over-
voltage
Overvolt F Lvl
59
%V
0…199
0
Allows the user to set a voltage (% of line
Voltage) that will cause a fault when the
voltage falls above this value. A zero value is
the “off” setting.
Over-
voltage
Overvolt F Dly
60
Secs
0…99
0
Allows the user the ability to prevent some
nuisance faults by entering a delay period that
provides a window that the voltage condition
must persist within for the controller to fault.
Over-
voltage
Overvolt A Lvl
61
%V
0…199
0
Allows the user to set a voltage (% of line
Voltage) that will cause an Alarm when the
voltage falls above this value. A zero value is
the “off” setting.
Over-
voltage
Overvolt A Dly
62
Secs
0…99
0
Allows the user the ability to prevent some
nuisance Alarms by entering a delay period
that provides a window that the voltage
condition must persist within for the controller
to Alarm.
Unbalance Unbalance F Lvl
63
%V
0…25
0
Allows the user to set a percentage of line to
line Voltages that will cause a fault when the
voltage falls above this value. A zero value is
the “off” setting.
Unbalance Unbalance F Dly
64
Secs
0…99
0
Allows the user the ability to prevent some
nuisance faults by entering a delay period that
provides a window that the voltage unbalance
condition must persist within for the controller
to fault.
Unbalance Unbalance A Lvl
65
%V
0…25
0
Allows the user to set a percentage of line to
line Voltages that will cause an Alarm when
the voltage falls above this value. A zero value
is the “off” setting.
Unbalance Unbalance A Dly
66
Secs
0…99
0
Allows the user the ability to prevent some
nuisance Alarms by entering a delay period
that provides a window that the voltage
unbalance condition must persist within for
the controller to Alarm.
Jam
Jam F Lvl
67
%FLC
0…1000
0
Allows the user to set an instantaneous over
current level (% of line FLC) that will cause a
fault. A zero value is the “off” setting.
Jam
Jam F Dly
68
Secs
0…99
0
Allows the user the ability to prevent some
nuisance faults by entering a delay period that
provides a window that the motor over current
condition must persist within for the controller
to fault.
Table B.1 Parameter List (Continued)
Group
Parameter
Name
Parameter
Number
Units
Min./
Max.
Default
Settings
Parameter Description
User
Settings
Summary of Contents for SMC-Flex
Page 1: ...USER MANUAL FOR SERIES B SMC Flex BULLETIN 150...
Page 4: ...Notes...
Page 30: ...1 22 Product Overview Notes...
Page 126: ...9 8 Troubleshooting...
Page 148: ...B 14 Parameter Information Notes...
Page 150: ...C 2 Renewal Parts Notes...
Page 156: ...E 2 Accessories Notes...