4-16
Programming
Example Settings
Undervoltage
➀
With Line Voltage programmed for 480V and the Undervoltage level
programmed for 80%, the trip value is 384V.
Overvoltage
➀
With Line Voltage programmed for 240V and the Overvoltage level
programmed for 115%, the trip value is 276V.
Jam
➁➂
With Motor FLC programmed for 150 A and the Jam level
programmed for 400%, the trip value is 600 A.
Underload
➁
With Motor FLC programmed for 90 A and the Underload level
programmed for 60%, the trip value is 54 A.
➀
The average value of the three phase-to-phase voltages is utilized.
➁
The largest value of the three phase currents is utilized.
➂
The SMC-Flex will self-protect.