Wiring
3-5
Power Lugs
Power lugs are required for devices rated 108..1250 A. In some cases
these lugs are sold in kits. Each kit contains three lugs. The number
and type of lugs required is listed in the following tables.
Table 3.C lists the recommended lugs for the SMC when configured
as a line connection. Table 3.D lists the recommended lugs when
using the SMC Flex with a delta connection. Note that devices rated
625…1250 A require the use of a power distribution block when used
with a delta connection.
2/T1
4/T2
6/T3
12/T6
8/T4
10/T5
M
3~
1/L1
5/L3
3/L2
IC
IC
IC
SMC-Flex
ATTENTION
!
Terminal covers are available for units rated
108…480 A which can make the product deadfront
(IP2X) safe. See Appendix D for the appropriate
catalog numbers for ordering.