Specifications
A-3
Short Circuit Protection
➀
Consult local codes for proper sizing of short circuit protection.
➁
Non-time delay fuses: Class K5 - 5…480 (8.7…831 A) devices,
Class L - 625…1250 (850…1600 A) devices.
➂
High capacity fault rating when used with time delay class CC, J, or L fuses.
SCPD Performance 200…600V
Protection Type
Type 1
SCCR List
➀
Non Time-Delay Fuse
Circuit Breaker
Time-Delay Fuse
Max. Std.
Available
Fault
Max. Std.
Fuse
(A)
➁
Max. Std.
Available Fault
Max. Circuit
Breaker
(A)
Max. High
Fault
Max. Fuse
(A)
➂
Line Device Operational Current Rating (A)
5
5 kA
20
5 kA
20
70 kA
10
25
5 kA
100
5 kA
100
70 kA
50
43
10 kA
150
10 kA
150
70 kA
90
60
10 kA
225
10 kA
225
70 kA
125
85
10 kA
300
10 kA
300
70 kA
175
108
10 kA
400
10 kA
300
70 kA
200
135
10 kA
500
10 kA
400
70 kA
225
201
18 kA
600
18 kA
600
70 kA
350
251
18 kA
700
18 kA
700
70 kA
400
317
30 kA
800
30 kA
800
69 kA
500
361
30 kA
1000
30 kA
1000
69 kA
600
480
42 kA
1200
42 kA
1200
69 kA
800
625
42 kA
1600
42 kA
1600
74 kA
1600
780
42 kA
1600
42 kA
2000
74 kA
1600
970
85 kA
2500
85 kA
2500
85 kA
2500
1250
85 kA
3000
85 kA
3200
85 kA
3000
Delta Device Operational Current Rating (A)
8.7
5 kA
35
5 kA
35
70 kA
17.5
43
5 kA
150
5 kA
150
70 kA
90
74
10 kA
300
10 kA
300
70 kA
150
104
10 kA
400
10 kA
400
70 kA
200
147
10 kA
400
10 kA
400
70 kA
200
187
10 kA
600
10 kA
500
70 kA
300
234
10 kA
700
10 kA
700
70 kA
400
348
18 kA
1000
18 kA
1000
70 kA
600
435
18 kA
1200
18 kA
1200
70 kA
800
549
30 kA
1600
30 kA
1600
69 kA
1000
625
30 kA
1600
30 kA
1600
69 kA
1200
831
42 kA
1600
30 kA
1600
69 kA
1600
850
42 kA
1600
42 kA
2000
74 kA
1600
900
42kA
1600
42 kA
2000
74 kA
1600
1200
85 kA
3000
85 kA
3200
85 kA
3000
1600
85 kA
3000
85 kA
3200
85 kA
3000
SCCR Performance 690V
Type 1
SCCR List
➀
Max. Std. Available Fault
Max. Ampere Tested — North American
Style
Max. Ampere Tested — European Style
Maximum FLC Device Rating (A)
108
70 kA
A070URD33xxx500
6,9 gRB 73xxx400 6,6URD33xxx500
135
70 kA
A070URD33xxx500
6,9 gRB 73xxx400 6,6URD33xxx500
201
70 kA
A070URD33xxx700
6,9 gRB 73xxx630 6,6URD33xxx700
251
70 kA
A070URD33xxx700
6,9 gRB 73xxx630 6,6URD33xxx700
317
70 kA
A070URD33xxx900
6,9 gRB 73xxx800 6,6URD33xxx900
361
70 kA
A070URD33xxx900
6,9 gRB 73xxx800 6,6URD33xxx900
480
70 kA
A070D33xxx1250 A100URD73xxx1250
9 URD 73xxx1250 6,6URD33xxx1250
625
70 kA
A070URD33xxx1400
6,6URD33xxx1400
780
70 kA
A070URD33xxx1400
6,6URD33xxx1400
970
85 kA
2 fuses in parallel A070URD33xxx1250
2 fuses in parallel 6,6URD33xxx1250
1250
85 kA
2 fuses in parallel A070URD33xxx1250
2 fuses in parallel 6,6URD33xxx1250
Summary of Contents for SMC-Flex
Page 1: ...USER MANUAL FOR SERIES B SMC Flex BULLETIN 150...
Page 4: ...Notes...
Page 30: ...1 22 Product Overview Notes...
Page 126: ...9 8 Troubleshooting...
Page 148: ...B 14 Parameter Information Notes...
Page 150: ...C 2 Renewal Parts Notes...
Page 156: ...E 2 Accessories Notes...