Programming
4-11
Programming Parameters
The following table provides the option-specific parameters that are
provided with each control option. These parameters are in addition
to those already discussed in the Basic Set Up and Metering groups.
Diagrams supporting the options described below are shown later in
this chapter.
Option
Parameter
Range
Standard
Soft Stop
SMC Option
This parameter identifies the type of
control present and is not user
programmable.
Standard
Soft Stop Time
Allows the user to set the time
period for the soft stopping function.
0…120 s
Preset Slow
Speed
SMC Option
This parameter identifies the type of
control present and is not user
programmable.
Standard
Slow Speed Select
Allows the user to program the slow
speed that best fits the application.
Low: 7% – forward,
10% – reverse
High: 15% – forward,
20% – reverse
Slow Speed Direction
This parameter programs the slow
speed motor rotational direction.
Forward, Reverse
Slow Accel Current
Allows the user to program the
required current to accelerate the
motor to slow speed operation.
0…450% of full load
current
Slow Running Current
Allows the user to program the
required current to operate the
motor at the slow speed setting.
0…450% of full load
current