Rockwell Automation Publication KNX-TD005A-EN-P - October 2021
13
Kinetix 6200 and Kinetix 6500 Modular Multi-axis Servo Drives
Contactor Ratings
This table provides the recommended contactor ratings for IAM power modules installed without a LIM module.
Input Transformer for Control Power
Input Power IEC (non-UL) Circuit-protection Specifications
Kinetix 6200 and Kinetix 6500 Drives
IEC (non-UL) Applications
IAM Power Module
Cat. No.
Drive Voltage
(three-phase) nom
Miniature CB
Cat. No.
Motor Protection CB
Cat. No.
Molded Case CB
Cat. No.
2094-BC01-MP5-M
360…480V
1492-SPM3D300
1489-M3D300
140M-F8E-C32
–
2094-BC01-M01-M
360…480V
140M-F8E-C32
2094-BC02-M02-M
360…480V
1492-SPM3D400
–
140M-F8E-C45
2094-BC04-M03-M
360…480V
N/A
–
140G-G6C3-C50
2094-BC07-M05-M
360…480V
140G-G6C3-C90
IAM Power Module
Cat. No.
Contactor
Cat. No.
2094-BC01-MP5-M
2094-BC01-M01-M
100-C23
x
10 (AC coil)
100-C23
xx
10 (DC coil)
2094-BC02-M02-M
100-C37
x
10 (AC coil)
100-C37
xx
10 (DC coil)
2094-BC04-M03-M
100-C60
x
10 (AC coil)
100-C60
xx
10 (DC coil)
2094-BC07-M05-M
100-C85
x
10 (AC coil)
100-C85
xx
10 (DC coil)
Attribute
Value
Cat. No.
(1)
(1) Variables (
xx-x
) determine the input voltage and wiring configuration.
Input volt-amperes
750VA
1497B-A10-
xx-x
-N
1000VA
1497B-A11-
xx-x
-N
1500VA
1497B-A12-
xx-x
-N
Input voltage
460V AC
Output voltage
120…240V AC