Kinetix 2090 Interface Cables
Dimensions - Kinetix 6000M Hybrid Cables
When installing hybrid cable runs, be careful not to stress the cable by making bends too sharp. Refer to the table below for bend radius definitions
and the dimension diagrams that follow when routing cables during system installation.
Hybrid and Network Cable Bend Radius Definitions
Hybrid Cable Dimensions
Type of Bend Radius
Type of Cable
Description
Static bend radius
Standard (non-flex)
The static (installation) bend radius and dimension B are 7 times the cable diameter:
• Do not begin a static bend inside dimension B.
• Use this measurement when routing the cable in a non-flex application between IDM units (the bend area).
– The bend area is where standard (non-flex) cables can be bent to their specified bend radius.
Hybrid Cable Dimensions
Hybrid Cable Cat. No.
A
mm (in.)
B
(1)
mm (in.)
(1) Dimension B is based on the cable diameter.
C
mm (in.)
D
mm (in.)
2090-CHBIFS8-12AA
xx
76.0 (3.0)
99.4 (3.9)
25.4 (1.0)
14.2 (0.5)
2090-CHBP8S8-12AA
xx
2090-CCPP8S8
2090-CBKS8-16AA03
56.7 (2.2)
8.1 (0.3)
D
C
2090-CHBIFS8-12AA
xx
12 AWG
A
A
38.1
(1.50)
2090-CHBP8S8-12AA
xx
12 AWG
2090-CBKS8-16AA
xx
16 AWG
A
2090-CCPP8S8-12AA
xx
12 AWG
A
B
B
B
B
B
B
B
B
Static Bend Radius
Dimensions are in mm (in.)
(reference only)
Typical End View
Cable
Diameter
Connector
Diameter
Cable Shield
(overall)
Cable Shield
(for control wires)
Bend Area
Bend Area
Bend Area
Bend Area
Static Bend Radius