Rockwell Automation Publication 520-UM001K-EN-E - August 2021
57
Chapter
2
Start Up
This chapter describes how to start up the PowerFlex 520-series drive. To
simplify drive setup, the most commonly programmed parameters are
organized in a single Basic Program Group.
Prepare for Drive Startup
Drive Startup Task List
1. Disconnect and lock out power to the machine.
2. Verify that AC line power at the disconnect device is within the rated
value of the drive.
3. If replacing a drive, verify the current drive’s catalog number. Verify all
options installed on the drive.
4. Verify that any digital control power is 24 volts.
5. Inspect grounding, wiring, connections, and environmental
compatibility.
6. Verify that the Sink (SNK)/Source (SRC) jumper is set to match your
control wiring scheme. See the
PowerFlex 523 Control I/O Terminal
and
PowerFlex 525 Control I/O Terminal Block on
for location.
7. Wire I/O as required for the application.
Topic
Page
Viewing and Editing Parameters
Smart Startup with Basic Program Group Parameters
LCD Display with QuickView Technology
IMPORTANT
General Precautions on page 13
section before proceeding.
ATTENTION:
Power must be applied to the drive to perform the following
start-up procedures. Some of the voltages present are at incoming line
potential. To avoid electric shock hazard or damage to equipment, only
qualified service personnel should perform the following procedure.
Thoroughly read and understand the procedure before beginning. If an
event does not occur while performing this procedure,
Do Not Proceed.
Remove All Power
including user supplied control voltages. User supplied
voltages may exist even when main AC power is not applied to the drive.
Correct the malfunction before continuing.
IMPORTANT
The default control scheme is Source (SRC). The Stop terminal is
jumpered to allow starting from the keypad or comms. If the control
scheme is changed to Sink (SNK), the jumper must be removed from I/O
Terminals 01 and 11 and installed between I/O Terminals 01 and 04.
Summary of Contents for Allen-Bradley PowerFlex 520 Series
Page 8: ...8 Rockwell Automation Publication 520 UM001K EN E August 2021 Table of Contents Notes ...
Page 68: ...68 Rockwell Automation Publication 520 UM001K EN E August 2021 Chapter 2 Start Up Notes ...
Page 236: ...236 Rockwell Automation Publication 520 UM001K EN E August 2021 Appendix F PID Set Up Notes ...
Page 270: ...270 Rockwell Automation Publication 520 UM001K EN E August 2021 Index Notes ...