Chapter 1 Installation/Wiring
Typical Multiple Drive Connection Examples
Input/Output
Connection Example
Multiple Digital Input
Connections
Customer Inputs can be
wired per External
Supply (SRC).
When connecting a single input such as Run, Stop, Reverse or Preset Speeds to multiple
drives, it is important to connect I/O Terminal 04 common together for all drives. If they are to
be tied into another common (such as earth ground or separate apparatus ground) only one
point of the daisy chain of I/O Terminal 04 should be connected.
Multiple Analog
Connections
When connecting a single potentiometer to multiple drives it is important to connect I/O
Terminal 14 common together for all drives. I/O Terminal 14 common and I/O Terminal 13
(potentiometer wiper) should be daisy chained to each drive. All drives must be powered up
for the analog signal to be read correctly.
Customer Inputs
Optional Ground Connection
04
02
04
02
04
02
ATTENTION:
I/O Common terminals should
not
be tied
together when using SNK (Internal Supply) mode. In SNK
mode, if power is removed from one drive, inadvertent
operation of other drives that share the same I/O Common
connection may occur.
Remote Potentiometer
Optional Ground Connection
12
13 14
13 14
13 14
Summary of Contents for Allen-Bradley PowerFlex 520 Series
Page 8: ...8 Rockwell Automation Publication 520 UM001K EN E August 2021 Table of Contents Notes ...
Page 68: ...68 Rockwell Automation Publication 520 UM001K EN E August 2021 Chapter 2 Start Up Notes ...
Page 236: ...236 Rockwell Automation Publication 520 UM001K EN E August 2021 Appendix F PID Set Up Notes ...
Page 270: ...270 Rockwell Automation Publication 520 UM001K EN E August 2021 Index Notes ...