Rockwell Automation Publication 520-UM001K-EN-E - August 2021
77
Chapter 3 Programming and Parameters
Basic Display Group
(continued)
b007 [Fault 1 Code]
Related Parameter(s):
b008 [Fault 2 Code]
b009 [Fault 3 Code]
A code that represents a drive fault. Codes appear in these parameters in the order they occur (
[Fault 1 Code] = the most recent fault). Repetitive faults are only
recorded once.
See
Values
Default:
Read Only
Min/Max:
F0/F127
Display:
F0
b010 [Process Display]
Related Parameter(s):
32 bit parameter.
Output frequency scaled by
[Process Disp Hi].
Scaled Process Value (PV) = (([Process Disp Hi] - [Process Disp Lo]) x ([Output Freq] - [Minimum Freq])) / ([Maximum Freq] - [Minimum Freq])
Values
Default:
Read Only
Min/Max:
0/9999.00
Display:
0.01
3
2
b011 [Process Fract]
Related Parameter(s):
Output frequency (fractional portion) scaled by
[Process Disp Hi].
Scaled Process Value (PV) = (([Process Disp Hi] - [Process Disp Lo]) x ([Output Freq] - [Minimum Freq])) / ([Maximum Freq] - [Minimum Freq])
Values
Default:
Read Only
Min/Max:
0.00/0.99
Display:
0.01