136
Rockwell Automation Publication 520-UM001K-EN-E - August 2021
Chapter 3 Programming and Parameters
Advanced Program Group
(continued)
A562 [Find Home Freq]
PowerFlex 525 only.
Sets the maximum frequency the drive uses when “Find Home” is issued.
Values
Default:
10.0 Hz
Min/Max:
0.1/500.0 Hz
Display:
0.1 Hz
PF 525
A563 [Find Home Dir]
Stop drive before changing this parameter.
PowerFlex 525 only.
Sets the direction the drive commands when “Find Home” is issued.
Options
0 “Forward” (Default)
1 “Reverse”
PF 525
A564 [Encoder Pos Tol]
PowerFlex 525 only.
Sets the “At Position” and the “At Home’ tolerance around the encoder count. The value is added to and subtracted from the target encoder unit value to create the
tolerance range.
Values
Default:
100
Min/Max:
1/50000
Display:
1
PF 525
A565 [Pos Reg Filter]
PowerFlex 525 only.
Sets the error signal filter in the position regulator.
Values
Default:
8
Min/Max:
0/15
Display:
1
PF 525
A566 [Pos Reg Gain]
PowerFlex 525 only.
Sets the gain adjustment for the position regulator.
Values
Default:
3.0
Min/Max:
0.0/200.0
Display:
0.1
PF 525
Summary of Contents for Allen-Bradley PowerFlex 520 Series
Page 8: ...8 Rockwell Automation Publication 520 UM001K EN E August 2021 Table of Contents Notes ...
Page 68: ...68 Rockwell Automation Publication 520 UM001K EN E August 2021 Chapter 2 Start Up Notes ...
Page 236: ...236 Rockwell Automation Publication 520 UM001K EN E August 2021 Appendix F PID Set Up Notes ...
Page 270: ...270 Rockwell Automation Publication 520 UM001K EN E August 2021 Index Notes ...