Chapter 3 Programming and Parameters
Terminal Block Group
(continued)
t091 [Anlg In 0-10V Lo]
Related Parameter(s):
Stop drive before changing this parameter.
Sets the percentage (based on 10V) of input voltage applied to the 0…10V analog input used to represent
[Minimum Freq].
Analog inversion can be accomplished by setting this value larger than
[Anlg In 0-10V Hi].
If
[10V Bipolar Enbl] is set to 1 “Bi-Polar In”, this parameter is ignored.
Values
Default:
0.0%
Min/Max:
0.0/200.0%
Display:
0.1%
t092 [Anlg In 0-10V Hi]
Related Parameter(s):
Stop drive before changing this parameter.
Sets the percentage (based on 10V) of input voltage applied to the 0…10V analog input used to represent
[Maximum Freq].
Analog inversion can be accomplished by setting this value smaller than
[Anlg In 0-10V Lo].
If
[10V Bipolar Enbl] is set to 1 “Bi-Polar In”, the same value applies to positive and negative voltage.
Values
Default:
100.0%
Min/Max:
0.0/200.0%
Display:
0.1%
t093 [10V Bipolar Enbl]
Related Parameter(s):
PowerFlex 525 only.
Enables/disables bi-polar control. In bi-polar mode direction is commanded by the polarity of the voltage.
If bi-polar control is enabled,
[Minimum Freq] and
[Anlg In 0-10V Lo] are ignored.
Options
0 “Uni-Polar In” (Default)
0…10V only
1 “Bi-Polar In”
±10V
PF 525
t094 [Anlg In V Loss]
Related Parameter(s):
Sets the response to a loss of input. When the 0…10V input (or –10 to +10V) is used for any reference, any input less than 1V is reported as a signal loss. Input must exceed
1.5V for the signal loss condition to end.
If enabled, this function affects any input that is being used as a speed reference, PID reference or PID setpoint in the drive.
Options
0 “Disabled” (Default)
1 “Fault (F29)”
2 “Stop”
3 “Zero Ref”
4 “Min Freq Ref”
5 “Max Freq Ref”
6 “Key Freq Ref”
7 “MOP Freq Ref”
8 “Continu Last”
t095 [Anlg In4-20mA Lo]
Related Parameter(s):
Stop drive before changing this parameter.
Sets the percentage (based on 4…20 mA) of input current applied to the 4…20 mA analog input used to represent
[Minimum Freq].
Analog inversion can be accomplished by setting this value larger than
[Anlg In4-20mA Hi].
Values
Default:
0.0%
Min/Max:
0.0/200.0%
Display:
0.1%
Summary of Contents for Allen-Bradley PowerFlex 520 Series
Page 8: ...8 Rockwell Automation Publication 520 UM001K EN E August 2021 Table of Contents Notes ...
Page 68: ...68 Rockwell Automation Publication 520 UM001K EN E August 2021 Chapter 2 Start Up Notes ...
Page 236: ...236 Rockwell Automation Publication 520 UM001K EN E August 2021 Appendix F PID Set Up Notes ...
Page 270: ...270 Rockwell Automation Publication 520 UM001K EN E August 2021 Index Notes ...