Chapter 4 Troubleshooting
Fault Indication
Manually Clearing Faults
Automatically Clearing Faults
Auto Restart (Reset/Run)
The Auto Restart feature provides the ability for the drive to automatically
perform a fault reset followed by a start attempt without user or application
intervention. This allows remote or “unattended” operation. Only certain
faults are allowed to be reset. Certain faults (Type 2) that indicate possible
drive component malfunction are not resettable. Fault types are listed in the
table
Fault Descriptions on page 159
for more
information.
Condition
Display
Drive is indicating a fault.
The integral LCD display provides visual notification of a fault condition by
displaying the following.
• Flashing fault number
• Flashing fault indicator (LED)
Press the Esc key to regain control of the display.
Step
Key(s)
1. Press Esc to acknowledge the fault. The fault information will be removed so that
you can use the integral keypad.
[Fault 1 Code] to view the most recent fault information.
2. Address the condition that caused the fault.
The cause must be corrected before the fault can be cleared. See
Descriptions, and Actions on page 159
3. After corrective action has been taken, clear the fault by one of these methods.
• Press Stop if
[Stop Mode] is set to a value between “0” and “3”.
• Cycle drive power.
[Fault Clear] to 1 “Reset Fault” or 2 “Clear Buffer”.
• Cycle digital input if
...
[DigIn TermBlk xx] is set to
13 “Clear Fault”.
Option/Step
Clear a Type 1 fault and restart the drive.
1. Set
[Auto Rstrt Tries] to a value other than “0”.
2. Set
[Auto Rstrt Delay] to a value other than “0”.
Clear an OverVoltage, UnderVoltage or Heatsink OvrTmp fault
without restarting the drive.
1. Set
[Auto Rstrt Tries] to a value other than “0”.
2. Set
[Auto Rstrt Delay] to “0”.
ATTENTION:
Equipment damage and/or personal injury may result if these
parameters are used in an inappropriate application. Do not use this
function without considering applicable local, national and international
codes, standards, regulations or industry guidelines.
FAULT
FWD
Esc
Sel
Esc
Summary of Contents for Allen-Bradley PowerFlex 520 Series
Page 8: ...8 Rockwell Automation Publication 520 UM001K EN E August 2021 Table of Contents Notes ...
Page 68: ...68 Rockwell Automation Publication 520 UM001K EN E August 2021 Chapter 2 Start Up Notes ...
Page 236: ...236 Rockwell Automation Publication 520 UM001K EN E August 2021 Appendix F PID Set Up Notes ...
Page 270: ...270 Rockwell Automation Publication 520 UM001K EN E August 2021 Index Notes ...