Chapter 1 Installation/Wiring
PowerFlex 523 Series B Control I/O Wiring Block Diagram
Control I/O Wiring Block Diagram Notes
(1) See
Digital Input Selection for Start Source on page 49
for more information on configuring the digital inputs.
IMPORTANT
I/O Terminal 01 is always a stop input. The stopping mode is determined by
the drive setting. See the tables below for more information.
Start Method
Stop Method
P046, P048, P050 [Start Source x]
I/O Terminal 01 Stop
Normal Stop
1 “Keypad”
Coast
Per P045
[Stop Mode]
2 “DigIn TrmBlk”
See
below
3 “Serial/DSI”
Coast
4 “Network Opt”
Coast
5 “EtherNet/IP”
(1)
(1) Setting is specific to PowerFlex 525 drives only.
Coast
04
05
06
01
02
03
11
12
13
14
15
C1
C2
Digital Common
DigIn TermBlk 05/Pulse
DigIn TermBlk 06
Stop
(1)
DigIn TermBlk 02/
Start/Run FWD
(2)
DigIn TermBlk 03/
Direction/Run REV
R1
R2
Relay N.O.
Relay Common
+24V DC
+10V DC
Analog Input
Analog Common
Analog Output
(3)
RJ45 Shield
Comm Common
+24V
+10V
Typical
SNK wiring
Typical
SRC wiring
R1
11
12
13
14
15
C1
C2
R2
R3
01
02
03
04
05
06
Pot must be
(4)
1...10 k ohm
2 W min.
4-20 mA
source
13
14
SNK
Digital In
DigIn
TermBlk 05 S
el
J7
J8
Pulse In
SRC
Digital
Input
SRC
SNK
R3
Relay N.C.
0/4-20 mA
Analog O
ut
J13
0-10V
4-20 mA
Analog In
J4
0-10V
81
RS485
(DSI)
0-10V
4-20 mA
0-10V
0/4-20 mA
Series B
Summary of Contents for Allen-Bradley PowerFlex 520 Series
Page 8: ...8 Rockwell Automation Publication 520 UM001K EN E August 2021 Table of Contents Notes ...
Page 68: ...68 Rockwell Automation Publication 520 UM001K EN E August 2021 Chapter 2 Start Up Notes ...
Page 236: ...236 Rockwell Automation Publication 520 UM001K EN E August 2021 Appendix F PID Set Up Notes ...
Page 270: ...270 Rockwell Automation Publication 520 UM001K EN E August 2021 Index Notes ...