65
99 M
MEESSSSAA IINN FFU
UNNZZIIO
ONNEE
CCoom
mpprreessssoorr ccaassiinngg rreessiissttaanncceess
Connect the compressor oil heating resistances at least 8 hours
before the compressor is to be started:
•
at the first unit start-up
•
after each prolonged period of inactivity
1 Power the heaters: isolator switch on 1 / ON.
2 Check the power consumption of the resistances to make sure
that they are functioning.
3 Start-up the compressor only if the crank-case temperature on
the lower side is be higher than the outside temperature by
at least 10°C .
4 Do not start the compressor with the crankcase oil below
operating temperature.
SSttaarrttiinngg rreeppoorrtt
Reading the objective operating conditions is useful for checking
the unit over time.
With unit of full load, namely in stable conditions and close to
those of work, take the following data:
•
Voltage and general absorptions with unit at full load
•
Absorption of varied electrical loads (compressors, fans,
pumps etc)
•
Temperatures and capacities of different liquid (water, air) in
the inlet and outlet of the unit.
•
Temperature and pressures on the characteristic points of the
refrigerating circuit (compressor discharge, liquid, intake).
The readings should be stored and made available during
maintenance .
22001144//6688//U
UEE PPEEDD ddiirreeccttiivvee
DIRECTIVE 2014/68/UE PED gives instructions for installers, users
and maintenance technicians as well.
Refer to local regulations; briefly and as an example, see the
following:
Compulsory verification of the first installation:
•
only for units assembled on the installer
’
s building site (for ex.
Condensing c direct expansion unit)
Certification of setting in service:
•
for all the units
Periodical verifications:
•
to be executed with the frequency indicated by the
Manufacturer (see the
“
maintenance inspections
”
paragraph)
99 M
MEESSSSAA IINN FFU
UNNZZIIO
ONNEE
FFiieelldd sseettttiinnggss
During installation, the unit settings and parameters should be configured by the installer to suit the installa-
tion configuration, climate conditions and end-user preferences.
The relevant settings are accessible and programmable through the FFO
ORR SSEERRVVIICCEEM
MAANN menu on the unit user
interface.
The user interface menus and settings can be navigated using the user interface
’
s touch-sensitive keys.
DDaannggeerr
Temperature values displayed on the wired controller (user interface) are in °C
KKeeyyss
FFuunnccttiioonn
M
MEENNU
U
Enter the menu structure from the home page
O
ONN // O
OFFFF
To set the ON / OFF functionor DHW mode turn on or off the function in the
menu structure
U
UNNLLO
OCCKK
Long press for unlocking /locking the controller
O
OKK
Go to the next step when programming a schedule in the menu structure /
confirm a selection/enter a submenu in the menu structure
SSXX -- DDXX
DDO
OW
WNN -- U
UPP
Navigate the cursor on the display/navigate in the menu structure/adjust the
settings
BBAACCKK
To return to the previous level.
Press to exit the current page and return to the previous page.
Long press to return straight to the home screen.
StaRt - up