CCoonnddeennssaattee ddrraaiinn
When a heat pump is running it produces a considerable amount
of water due to the defrosting cycles of the external coil.
NNO
OTTEE
The condensation must be eliminated in a manner to avoid
wetting pedestrian areas.
With extensive very cold outdoor temperatures, condensation
could freeze outside the unit blocking the flow and causing a
slow build-up of ice; therefore special attention must be paid to
eliminating condensation, raising the unit off the ground and
evaluating whether antifreeze elements should be installed.
To avoid freezing of the water downstream of the drain lay the
tube below the frost line (EE).
A DTX = Condensation collection basin (Accessory separately
supplied)
B Unit support ((Accessory separately supplied)
C Pipe discharge connection (Customer care)
D Condensate discharge connection Ø 30
E Frost line
F Layer of gravel or pebbles to help with condensate drainage
G This drain hole is covered by rubber plug. If the small drain
hole can not meet the drainage requirements, the big drain
hole can be used at the same time.
L
’
unità può essere fornita con:
DT-HS2 - Bacinella raccolta condensa
(accessorio fornito separatamente)
D
Size HS004 - HS006
Size HS008 - HS016
D
E
F
Remove panel
Remove screws A
A
A
RReem
moovvee tthhee ccoom
mpprreessssoorr ffiixxiinngg bbrraacckkeett
((ssiizzee HHSS001122--HHSS001166))
D
G
inStaLLation RequiRementS