This filter is usually placed in the part with the larger flow. A
tissue filter is designed to catch the finer particles.
EExxcclluussiioonnss
The warranty does not cover damage formed by limestone,
deposits and impurities deriving from the water supply and/or
by the malfunctioning of the system cleaning system.
NNoottee
If necessary, fit a water softener to reduce water hardness.
RRiisskk ooff ffrroosstt
NNoottee
When the outside temperature gets close to 0°C, the water
in the pipes and unit may freeze.
Frost may determine irreversible damage to the unit.
Frost damage is not covered by the warranty.
If the unit or hydraulic connections are subject to temperatures
close to 0°C:
•
mix water with glycol, or
•
safeguard the pipes with heating cables placed under the
insulation, or
•
empty the system in cases of long non-use
AAnnttii--ffrreeeezzee ssoolluuttiioonnss
Consider that the use of anti-freeze solution determines an
increase in a pressure drop.
Make sure that the glycol type utilized is inhibited (not
corrosive) and compatible with the water circuit components.
Do not use different glycol mixture (i.e. ethylene with propylene).
2
2
4
6
33--wwaayy vvaallvvee
SSyysstteem
m vveenntt
SSyysstteem
m cchhaarrggee hheeaattiinngg//ccoooolliinngg
1 Switch ON the unit
2 From the keyboard put ON the domestic hot water mode and
wait until the lever of the 3 way valve goes to the right,
3 Switch OFF the unit
4 Press on the lever and move it to the centre until it locks
5 Start filling; open the filling tap located on the system
6 Open the flow and return taps located on the system
7 Open the vent valves of the terminals or radiators
8 Close them when water begins to exit; continue the charging
until the pressure intended for the system (max.3 bar).
9 Check the hydraulic seal of the joints.
•
Once the process is finished, the valve goes to heating/
cooling mode automatically when will be power on.
•
Repeat the operation after the unit has operated for a number
of hours and periodically control the system pressure.
Reintegration is carried out when the unit is off (pump OFF).
DDoom
meessttiicc hhoott wwaatteerr ttaannkk cchhaarrggee
Maximum DWH system pressure 6 bar
DWH saftey valve setting 6 bar
1 System general switch = OFF.
2 Close the drain valve
3 Start filling; open the DHW filling tap located on the system
4 Open the taps located on the system and connected to the
DHW outlet, DHW recirculation inlet and water inlet
5 Open the hot water taps (bathroom and kitchen)
6 Close the taps when water starts to come out.
7 Check the hydraulic seal of the joints.
WateR connectionS