Sound levels refer to units with full load under nominal test conditions. Data referred to the following conditions:
entering / leaving exchanger water temperature user side 47/55°C source side exchanger air inlet 7°C.
The sound pressure level refers to a distance of 1m from the external surface of the units operating in an open field.
Noise levels are determined using the tensiometric method (UNI EN ISO 9614-2).
SSoouunndd ppoowweerr lleevveell
SSoouunndd pprreessssuurree
lleevveell
SSoouunndd ppoowweerr lleevveell
SSIIZZEE
O
Occttaavvee bbaanndd ((HHzz))
6633
112255
225500
550000
11000000
22000000
44000000
88000000
ddBB((AA))
ddBB((AA))
HHSS000044
46
49
49
52
52
46
37
27
42
55
HHSS000066
49
48
50
55
53
48
39
30
44
57
HHSS000088
36
51
53
56
55
49
44
30
45
58
HHSS001100
37
56
53
57
57
51
47
36
47
60
HHSS001122
44
53
54
60
58
55
52
51
50
63
HHSS001144
44
54
55
60
59
57
56
54
51
64
HHSS001166
46
58
57
60
61
59
54
51
53
66
SSIIZZEE
SSoouunndd pprreessssuurree
lleevveell
SSoouunndd ppoowweerr lleevveell
ddBB((AA))
ddBB((AA))
HHSS000044
40
53
HHSS000066
40
53
HHSS000088
42
55
HHSS001100
42
55
HHSS001122
46
59
HHSS001144
47
60
HHSS001166
48
61
Sound levels refer to units with full load under nominal test conditions. For
maximum capacity delivered in silent mode use a correction factor of 0.8.
Data referred to the following conditions: entering / leaving exchanger
water temperature user side 47/55°C source side exchanger air inlet 7°C.
The sound pressure level refers to a distance of 1m from the external
surface of the units operating in an open field.
Noise levels are determined using the tensiometric method (UNI EN ISO
9614-2).
SSIIZZEE
SSoouunndd pprreessssuurree
lleevveell
SSoouunndd ppoowweerr lleevveell
ddBB((AA))
ddBB((AA))
HHSS000044
37
50
HHSS000066
38
51
HHSS000088
39
52
HHSS001100
39
52
HHSS001122
41
54
HHSS001144
41
54
HHSS001166
41
54
Sound levels refer to units with full load under nominal test conditions. For
maximum capacity delivered in silent mode use a correction factor of 0,6
Data referred to the following conditions: entering / leaving exchanger
water temperature user side 47/55°C source side exchanger air inlet 7°C.
The sound pressure level refers to a distance of 1m from the external
surface of the units operating in an open field.
Noise levels are determined using the tensiometric method (UNI EN ISO
9614-2).
SSoouunndd lleevveellss oouuttddoooorr uunniitt
SSttaannddaarrdd m
mooddee
SSiilleenncceedd m
mooddee
SSuuppeerr--ssiilleenncceedd m
mooddee
technicaL data