133
1100 RREEGGO
OLLAAZZIIO
ONNEE
217
t_TBH_delay
Default: 30min range: 0~240min ; adjustment interval 5min
218
dT5S_TBH_off
Default: 5°C, range: 0 ~ 10°C, adjustment interval 1°C
219
T4_TBH_on
A series: Default: 5°C, range: -5 ~ 50°C;
E series: Default: 5°C, range: -5~20°C; adjustment interval 1°C
220
T5s_DI
Sterilization function water tank set temperature, setting range 60~70°C,
default 65 °C
222
t_DI_hightemp
Sterilization high temperature time, setting range: 5~ 60 min , default
15min
223
t_interval_C
Cooling mode compressor start time interval; range: 5~5min , default value
is 5min
224
dT1SC
Default: 5°C, range: 2-10°C, adjustment interval 1°C
225
dTSC
Default: 2°C, range: 1-10°C, adjustment interval 1°C
226
T4cmax
Default: 52°C, range: 35-52°C; adjustment interval 1°C
227
T4cmin
Default: 10°C, range: -5-25°C; adjustment interval 1°C
228
t_interval_H
Heating mode compressor start time interval; range: 5~60min, default is 5
min
229
dT1SH
A series: Default: 5°C, range: 2- 20°C;
E series: Default: 5°C, range: 2-10°C; adjustment interval 1°C
230
dTSH
Default: 2°C, range: 1-10°C, adjustment interval 1°C
231
T4hmax
Default: 25°C, range: 20-35°C, adjustment interval 1°C
232
T4hmin
A series: Default: -1.5°C, range: -25-30°C, adjusted spacing . 1°C
E Series: Default: -1.5°C, range: -25-15°C, adjusted spacing . 1°C
233
T4_IBH_on
The ambient temperature of the electric auxiliary heating IBH of the
hydraulic module is turned on, the setting range: -15~10°C, the default
value: -5°C
234
dT1_IBH_on
Hydraulic module electric auxiliary heating IBH opening temperature hyste-
resis, setting range: 2~10°C the default value is 5°C
235
t_IBH_delay
Hydraulic module electric auxiliary heating IBH delay opening time, setting
range: 15~120min , default value 30min
236
t_IBH12_delay
RESERVED
237
T4_AHS_on
The external heat source AHS turns on the ambient temperature,
A series: Range -15 ~ 30°C,
E series: setting range -15 ~ 10°C,
Rinnai model default value is 10°C, Midea model -5°C
238
dT1_AHS_on
The external heat source AHS turns on the temperature difference,
A series: Range: 2 ~ 20°C, the default value . 5°C
E series: Setting range: 2~10°C, the default value is 5°
239
dT1_AHS_off
RESERVED
240
t_AHS_delay
The time that the compressor has run before starting the additional heat-
ing source, setting range 5~120min, default value 30min
241
t_DHWHP_max
The maximum time for the heat pump to run hot water, the setting range:
10~600min ; default value: 120min; setting value is minute
242
t_DHWHP_restrict
Maximum operating time of the heat pump in heating/cooling mode.
The setting range is: 10~600min; the default value is 30min; the setting
value is minute.
1100 RREEGGO
OLLAAZZIIO
ONNEE
243
T4autocmin
The default value is: 25°C, the range is: 20~29°C, the adjustment interval
is 1°C.
244
T4autohmax
The default value is: 17°C, the range is: 10~17°C, the adjustment interval
is 1°C.
245
T1S_H.A_H
T1 set value in heating mode during vacation, range: 20~25°C, default
25°C
246
T5S_H.A_DHW
T5 set value in hot water mode during vacation, range: 20~25°C, default
25 °C
247
Start percentage
The range is 10-100 , the default is 10. The adjustment interval is 10
248
Adjustment time
Range 1-60 default 5
249
dTbt2
Range 0-50 default 15
250
IBH1 power
Range 0-200 , default 0 , unit 100W
251
IBH2 power
Range 0-200 , default 0 , unit 100W
252
TBH power
Range 0-200 , default 0 , unit 100W
253
Comfort parameter
Reserved, query the register and report address error
254
Comfort parameter
Reserved, query the register and report address error
255
t_DRYUP
Heating days, setting range: 4~15 days, default 8 days
256
t_HIGHPEAK
Drying days, setting range: 3~7 days, default 5 days
257
t_DRYD
Cooling days, setting range: 4~15 days, default 5 days
258
T_DRYPEAK
Maximum drying temperature, setting range: 30-55°C, default 45°C
259
t_firstFH
Floor heating first run time, default value 72hrs, setting range: 48-96hrs
260
T1S(First warm)
Target outlet water temperature in preheating for floor mode: setting
range: 25~35°C, default: 25°C;
261
T1SetC1
Cooling temperature curve 9 parameters, setting range 5-25°C, default 10°C
262
T1SetC2
Cooling temperature curve 9 parameters, setting range 5-25°C, default 16°C
263
T4C1
Cooling temperature curve 9 parameters, setting range (-5)-46°C, default
35°C
264
T4C2
Cooling temperature curve 9 parameters, setting range (-5)-46°C, default
25°C
265
T1SetH1
Heating temperature curve 9 parameters, setting range 25-60°C, default
35°C
266
T1SetH1
Heating temperature curve 9 parameters, setting range 25-60°C, default
28°C
267
T4H1
Heating temperature curve 9 parameters, setting range (-25)-35°C, default
-5°C
268
T4H2
Heating temperature curve 9 parameters, setting range (-25)-35°C, default
7°C
269
Current limiting scheme,
0= No setting;
1~8= Scheme 1~8,
default 0
270
HB: t_T4_FRESH_C
Range 0.5-6hour , adjustment interval 0.5 , sending value = actual value *2
LB: t_T4_FRESH_H
Range 0.5-6hour , adjustment interval 0.5 , sending value = actual value *2
271
T_PUMPI_DELAY
Range 2-20 , adjustment interval 0.5 , sending value = actual value *2
272
EMISSION TYPE
Bit12-15 : Zone 2 cooling terminal type
Bit8-11 : Zone 1 cooling terminal type
Bit4-7 : Zone 2 heating terminal type
Bit0-3 : Zone 1 heating terminal type
contRoL