154
1144 IINNFFO
ORRM
MAAZZIIO
ONNEE TTEECCNNIICCHHEE
SSIIZZEE
HHSS000044
HHSS000066
HHSS000088
HHSS001100
HHSS001122** HHSS001144** HHSS001166**
SSttoorraaggee ttaannkk ccaappaacciittyy
190 L 250 L 190 L 250 L 190 L 250 L 190 L 250 L 250 L
250 L
250 L
EErrPP
AAvveerraaggee cclliim
maattee ccoonnddiittiioonnss -- HHeeaatt ppuum
mppss ffoorr HHiigghh tteem
mppeerraattuurree aapppplliiccaattiioonnss
Nominal power
7 kW
4
6
7
9
12
13
13
SCOP
7
-
3.32
3.54
3.72
3.73
3.56
3.52
3.48
Generator energy class
7
-
A++
A++
A++
A++
A++
A++
A++
η
s
7 %
130
138
146
146
139
138
136
System energy class
7
-
A++
A++
A++
A++
A++
A++
A++
η
s
7 %
135
143
151
151
144
143
141
AAvveerraaggee cclliim
maattee ccoonnddiittiioonnss -- HHeeaatt ppuum
mppss ffoorr LLooww tteem
mppeerraattuurree aapppplliiccaattiioonnss
Nominal power
8 kW
6
8
10
12
14
16
5
SCOP
8
-
5,13
5,15
5.32
5.27
5.00
4.91
4.89
Generator energy class
8
-
A+++
A+++
A+++
A+++
A+++
A+++
A+++
η
s
8 %
202
203
210
208
196
193
193
System energy class
8
-
A+++
A+++
A+++
A+++
A+++
A+++
A+++
η
s
8 %
207
208
215
213
201
198
198
AAvveerraaggee cclliim
maattee ccoonnddiittiioonnss -- HHeeaatt ppuum
mpp ffoorr ffaann ccooiill aapppplliiccaattiioonnss
Nominal power
9 kW
4
6
7
9
12
13
14
SEER
9
-
5,09
5,42
5.95
6.01
5.16
5.10
4.87
Generator energy class
9
-
A+++
A+++
A+++
A+++
A+++
A+++
A+++
η
s
9 %
201
214
235
238
203
201
192
HHeeaatt ppuum
mpp ffoorr ddoom
meessttiicc hhoott wwaatteerr aapppplliiccaattiioonnss
Declared load profile
10 -
L
XL
L
XL
L
XL
L
XL
XL
XL
XL
η
wh
10 %
120
123
120
123
116
125
116
125
124
124
124
Domestic Hot Water Energy
Class
10 -
A+
A+
A+
A+
A+
A+
A+
A+
A+
A+
A+
7 The product is conforming with the European ErP Directives, which includes Commission Delegated Regulation (EU) N. 811/2018 and
Commission Delegated Regulation N. 813/2018, Clima Average, High Temperature 47/55°C
8 The product is conforming with the European ErP Directives, which includes Commission Delegated Regulation (EU) N. 811/2018 and
Commission Delegated Regulation N. 813/2018, Clima Average, Low Temperature 30/35°C
9 The product is conforming with the European ErP Directives, which includes Commission Delegated Regulation (EU) N. 811/2018 and
Commission Delegated Regulation N. 813/2018, Clima Average, Clima Average, Low temperature 12/7°C
10 Data in accordance: EN 16147:2017
* All data calculated with zero height difference and equivalent length of 7m.
1 User side entering/leaving water temperature 30/35 °C, source side air 7°C (U.R. = 85% Heat power data, Total power input and COP
in accordance with EN 14511:2018
2 User side entering/leaving water temperature 30/35 °C, source side air -7°C Heat power data, Total power input and COP in
accordance with EN 14511:2018
3 User side entering/leaving water temperature 40/45 °C, source side air 7°C (U.R. = 85% Heat power data, Total power input and COP
in accordance with EN 14511:2018
4 User side entering/leaving water temperature 18/23 °C, source side air 35°C Heat power data, Total power input and COP in
accordance with EN 14511:2018
5 User side entering/leaving water temperature 7/12 °C, source side air 35°C Heat power data, Total power input and COP in
accordance with EN 14511:2018
6 The product is conforming with the European ErP Directives, which includes Commission Delegated Regulation (EU) N. 811/2018 and
Commission Delegated Regulation N. 813/2018, Clima Average, High Temperature 47/55°C
* All data calculated with zero height difference and equivalent length of 7m.
technicaL data