58
TECHNICAL ASSISTANCE SERVICE
Error
code
via QAA
Diagnostic
info
Description of error
Type of fault
System action
Procedure
130
508
Flue gas temperature
threshold exceeded
TaAbschal parameter
(flue gas temperatu-
re threshold for boiler
shutdown) exceeded
Safety shutdown
Check the flue gas vent;
check the temperatu-
re sensor; check the
burner; check setting of
parameter 592
130
509
Flue gas temperature
threshold exceeded
TaBegrenz parameter (flue
gas temperature th-
reshold for reducing heat
output) exceeded
Message
Check the flue gas vent;
check the temperatu-
re sensor; check the
burner; check setting of
parameter 591
132
77
Water pressure switch
tripped
The input has been con-
figured as a switch that
prevents start-up (FaEin-
stellFlags2) and the switch
is open
Safety shutdown
Check the system pres-
sure
132
92
Water pressure switch
tripped
The input has been con-
figured as a switch that
prevents start-up (FaEin-
stellFlags2) and the switch
is open
Safety shutdown
Check the system pres-
sure
132
93
Water pressure switch
tripped
The pressure switch has
been configured as a
switch that prevents start-
up (FaEinstellFlags2) and
the switch is open during
safety time
Safety shutdown
Check the system pres-
sure
132
94
Water pressure switch
tripped
The pressure switch has
been configured as a
switch that prevents start-
up (FaEinstellFlags2) and
the switch is open during
safety time. Start-up pre-
vented for two hours
Safety shutdown
Check the system pres-
sure
132
285
Water pressure switch
tripped
Shutdown at wrong time.
The error masking time
has been interrupted
Safety shutdown
Check the system pres-
sure
133
101
No flame
The flame does not appe-
ar at the end of the safety
time--> Repetition
Safety shutdown
Check the connections
to the burner
133
102
No flame
The flame does not appe-
ar at the end of the safety
time
Burner lockout
(permanent).
Lockout reset re-
quired
Check the connections
to the burner
140
521
Illegal LPB address
Illegal segment number or
LPB device number
Message
Contact Technical Assi-
stance Service
148
517
Interface/base unit
LPB incompatibility
LPB incompatibility
between interface unit
and base unit
Message
Contact Technical Assi-
stance Service
151
1
Internal control board
error
Software error or internal
error
Can be a Mes-
sage or a Safety
Shutdown or
a (permanent)
burner lockout
with manual reset
request
Contact Technical Assi-
stance Service
151
…
Internal control board
error
Software error or internal
error
Can be a Mes-
sage or a Safety
Shutdown or
a (permanent)
burner lockout
with manual reset
request
Contact Technical Assi-
stance Service