TECHNICAL ASSISTANCE SERVICE
Error
code
via QAA
Diagnostic
info
Description of error
Type of fault
System action
Procedure
110
17
Safety thermostat
tripped (SLT)
Circuit open
Burner lockout
(permanent).
Lockout reset re-
quired
Circuit open: check con-
nections
110
115
Safety thermostat
tripped (SLT)
Maximum temperature
exceeded
Safety shutdown
SLT thermostat tripped:
check system
110
129
Safety thermostat
tripped (SLT)
Thermostat tripped due to
residual heat
Burner lockout
(permanent).
Lockout reset re-
quired
SLT thermostat tripped
at wrong time: check
system
110
422
Safety thermostat
tripped (SLT)
Thermostat tripped due to
residual heat
Burner lockout
(permanent).
Lockout reset re-
quired
SLT thermostat tripped
at wrong time: check
system
110
470
Safety thermostat
tripped (SLT)
Circuit open
Safety shutdown
SLT thermostat tripped:
check system
111
141
Threshold thermostat
tripped
Threshold thermostat
tripped
Safety shutdown
Temperature too high:
check system
113
506
Flue gas thermostat
tripped
TaAbschal (flue gas
temperature threshold
for boiler shutdown)
parameter exceeded or
reading not plausible
Burner lockout
(permanent).
Lockout reset re-
quired
Check flue gas vent;
check temperature
reading; check/replace
temperature sensor
117
512
Water pressure too
high (inactive)
PH2Omax (maximum
water pressure in boiler)
parameter exceeded
Safety shutdown
Check the water pres-
sure; check the system;
check/replace the tem-
perature sensor
117
537
Water pressure too
high (inactive)
dpH2OmaxPuOn parame-
ter (maximum permissible
pressure differential after
pump start-up) exceeded
Safety shutdown
Check the water pres-
sure; check the system;
check the pressure
switch
118
513
Water pressure too
low (inactive)
Water pressure is below
the value set in the PH2O-
Abschalt parameter (mini-
mum pressure threshold
for deactivating the boiler
pump)
Safety shutdown
Check the water pres-
sure; check the system;
check the pressure
switch; check the pump
118
514
Water pressure too
low (inactive)
Water pressure is below
the value set in the PH2O-
min parameter (minimum
pressure)
Message
Check the water pres-
sure; check the system;
check the pressure
switch; check the pump
118
536
Water pressure too
low (inactive)
Water pressure is be-
low the value set in the
dpH2OminPuOn parame-
ter (minimum pressure
differential after pump
start-up)
Safety shutdown
Check the water pres-
sure; check the system;
check the pressure
switch; check the pump
119
139
Flue gas thermostat
tripped
Flue gas thermostat
tripped
Burner lockout
(permanent).
Lockout reset re-
quired
Check the water pres-
sure; check the system;
check the temperature
sensor
119
140
Flue gas thermostat
tripped
Flue gas thermostat
tripped
Safety shutdown
Check the water pres-
sure; check the system;
check the temperature
sensor
128
98
No flame during fun-
ctioning
Flame failure during fun-
ctioning
Safety shutdown
Check the gas supply
and gas valve status;
check the burner