TECHNICAL ASSISTANCE SERVICE
− Press the
D
key.
The fan switches to minimum speed.
− Set the CO
2
level by turning the adjuster screw (2)
on the gas valve with a TORX40 key. Turn anti-
clockwise to reduce CO
2
, clockwise to increase
CO
2
.
Once the adjustments are complete, the
combustion parameters should be as specified
in the tables below.
4
CO
2
values for functioning at MINIMUM POWER
TAU 35 UNIT
G20
9,15
G31
9,90
− Press
V
or
M
to return to normal functioning
mode.
Once all adjustments have been made:
− Carefully screw the plug back on the combustion
analysis socket
− Fit the top panel back on.
9