55
TECHNICAL ASSISTANCE SERVICE
Error
code
via QAA
Diagnostic
info
Description of error
Type of fault
System action
Procedure
92
294
Electronic device
errors
Hardware error
Burner lockout
(permanent).
Lockout reset re-
quired
Contact Technical Assi-
stance Service
92
484
Electronic device
errors
Room thermostat input
faulty
Message
Contact Technical Assi-
stance Service
92
485
Electronic device
errors
Air pressure switch input
faulty
Message
Contact Technical Assi-
stance Service
92
486
Electronic device
errors
Gas pressure switch input
faulty
Message
Contact Technical Assi-
stance Service
92
487
Electronic device
errors
Safety relay output faulty
Message
Contact Technical Assi-
stance Service
92
488
Electronic device
errors
Safety valve output faulty
Message
Contact Technical Assi-
stance Service
92
489
Electronic device
errors
DHW flow switch input
faulty
Message
Contact Technical Assi-
stance Service
92
490
Electronic device
errors
CH flow switch input
faulty
Message
Contact Technical Assi-
stance Service
92
491
Electronic device
errors
Dynamic ignition output
faulty
Message
Contact Technical Assi-
stance Service
95
538
Invalid date
Internal LMU clock invalid
Message
Contact Technical Assi-
stance Service
100
520
Two master clocks
found
Two master clocks found
on LPB connection
Message
Contact Technical Assi-
stance Service
100
539
Two master clocks
found
Two master clocks found
(on Qaa)
Message
Contact Technical Assi-
stance Service
105
560
Maintenance mes-
sage
The hours of functioning
exceed the number set at
the last service
Message
Service the boiler
105
561
Maintenance mes-
sage
The burner ignitions
exceed the number set at
the last service
Message
Service the boiler
105
562
Maintenance mes-
sage
The months of functioning
exceed the number set at
the last service
Message
Service the boiler
105
563
Maintenance mes-
sage
The flame ionisation cur-
rent has been exceeded
Message
Service the boiler