TECHNICAL ASSISTANCE SERVICE
52
CAuSE
SOluTION
FAulT
Burner badly adjusted
- Check adjustment of burner
(perform flue gas analysis)
Flue blocked
- Clean flue pipes
Burner air intake dirty
- Clean burner air intake
The boiler gets dirty
very quickly
Burner dirty
- Clean combustion chamber
Insufficient air/fuel flow to burner
- Check and adjust burner
Boiler temperature
setpoint incorrect
- Select correct temperature set-
point
The boiler does not reach its
temperature setpoint
Boiler temperature
setpoint incorrect
- Select correct temperature set-
point
- Check electrical wiring
- Check positions of sensors
No water supply
- Check automatic vent and manu-
al bleed valves
- Check CH circuit pressure
The safety thermostat trips
repeatedly
Fumes escaping into the air
- Check that burner body is clean
- Check that flue pipes are clean
- Check condition of boiler seals
- Check quality of combustion
There is a smell of fumes
Air in circuit
- Bleed circuit
Pump malfunctioning
- Unseize pump
- Replace pump
The boiler reaches the set
temperature but the radiators
are still cold