TECHNICAL ASSISTANCE SERVICE
38
On models 26 BK and 35 BK:
- Turn the (
I
)Summer/(
II
)Winter selector to (
II
) Winter.
- Turn the function selector to ON (
II
) and make sure that
the green power indicator lights.
The burner should ignite and remain in operation until the
temperature setpoint is reached.
If any ignition or functioning errors occur, the burner
performs a “LOCK-OUT” and the red LED on the control
panel comes on to indicate this.
b
If a “LOCK-OUT” occurs, wait about 30 seconds
before resetting the burner.
To reset the burner, press the button light on the burner.
Wait for the burner to complete the entire start-up cycle
again, up to the ignition of the flame.
IMPORTANT
Before it starts pre-ventilation (pre-purging), the oil burner
pre-heats the fuel oil for about 2 and half minutes.
The first time the burner starts up for the winter, ignition
problems can occur if the temperature of the fuel oil is
below 8°C.
After the burner has started up 2 or 3 times, the tem-
perature of the supply increases and these problems
disappear.
20
40
60
80
100
0
120
20
40 60 80
100
4
3 2 1
0
0
120
20
40
60
80
100
0
120
20
40
60
80
100
0
120