TECHNICAL ASSISTANCE SERVICE
47
Thermostat
Heating element
Motor
Ignition transformer
Valve
Flame detected
Lockout indicator
Power supply
Thermostat
Heating element
Motor
Ignition transformer
Valve
Flame detected
Lockout indicator
Power supply
A normal functioning cycle
A
Lockout because of ignition failure
0 ÷ 150s
0 ÷ 150s
~
5s
~
12s
~
12s
A normal functioning cycle
B
~
12s
FUNCTIONING PROGRAM
b
If the flame does not ignite within the safety time (5 seconds), the burner controller enters lockout and the red light
button (1) lights.
Press the light button (1) to reset the burner controller.
b
Functioning cycle
A
is only valid for initial start-up and for start-ups after a burner lockout or thermostat
lockout. For all subsequent startups, functioning cycle
B
applies, in which the motor starts up as soon as
the control thermostat closes.
1