Radio Frequency Systems
BD210WLP Series Air Dryer User’s Guide
Page 98 of 101
100518832 – Rev. B
14.4 SNMP Parameters
Device Configuration Information
Device ID
Alphanumeric (Defined by Customer)
Device Model
Alphanumeric (Factory Preset)
Device Firmware Version
Numeric (Factory Preset)
Current Date/Time
Numeric (mm/dd/yy hh:mm)
IP Address
Numeric (xxx.xxx.xxx.xxx)
Subnet Mask
Numeric (xxx.xxx.xxx.xxx)
Gateway Address
Numeric (xxx.xxx.xxx.xxx)
SNMP Trap Server Address
Numeric (xxx.xxx.xxx.xxx)
SNMP Read Community String
(also sets SNMP Trap Community String)
Alphanumeric (6-14 digits, Default =
“public”)
SNMP Write Community
Alphanumeric (6-14 digits, Default =
“123456”
Status Readings (Read-Only)
Outlet Pressure Reading
Numeric (PSI (KPa))
Tank Pressure Reading
Numeric (PSI (KPa))
Humidity Reading
Numeric (%)
Cabinet Temperature Reading
Numeric (DEG F (DEG C))
Duty Cycle Reading
Numeric (%)
Compressor Total Run Time Reading
Numeric (Hours)
Compressor Last Run Time Reading
Numeric (Seconds)
System Status
ON / SHUTDOWN
Compressor Status
ON / OFF
Fan Status
ON / OFF
Alarm Readings (Read-Only)
High Humidity Alarm
OK / Alarm
High Outlet Pressure Alarm
OK / Alarm
Low Outlet Pressure Alarm
OK / Alarm
High Cabinet Temperature Alarm
OK / Alarm
Duty Cycle Alarm
OK / Alarm
High Compressor Last Run Time Alarm
OK / Alarm
Maintenance Required Alarm
OK / Alarm
Total Alarm
OK / Alarm
Configuration Settings (Read-Write)
High Humidity Alarm Threshold
Numeric (%)
High Outlet Pressure Alarm Threshold
Numeric (PSI (KPa))
Low Outlet Pressure Alarm Threshold
Numeric (PSI (KPa))
Duty Cycle Alarm Threshold
Numeric (%)
High Compressor Last Run Time Alarm Threshold
Numeric (Seconds)
Reset Compressor Total Run Time Reading
Numeric (Hours)
Start Up Delay
Numeric (Seconds)
Alarm Reset
RESET
Alarm Delay
ON / OFF
Alarm Traps Sent to SNMP Server
High Humidity
High Outlet Pressure
Low Outlet Pressure
High Cabinet Temperature
High Duty Cycle
High Compressor Last Run Time
Maintenance Required