Point Number:
the field specifies the DNP3 identifier for each binary
Output channel. The valid range is 0-65535. The Point Number must be
unique for each Binary Input Channel. Note that the same Point
Number is also used by a matching DNP3 Frozen Counter point.
Static Variation:
the field defines the data object returned in response
to a DNP3 static data poll request (e.g. Class 0 request). This attribute
must be defined for each counter point. The following table lists the
valid types for Binary Input point types:
Static Object Type
Group Variation Description
g20v1 32b Counter
20
1
32-bit Counter with Status
g20v2 16b Counter
20
2
16-bit Counter with Status
g20v5 32b Counter
No Flag
20
5
32-bit Counter
g20v6 16b Counter
No Flag
20
6
16-bit Counter
Data Class:
the point Data Class attribute affects the way the data is
reported externally from the Universal Hub. If a point configuration has
a point data class other than Local, changes will be reported to the
SCADA Master in the indicated DNP3 data class. As per DNP3 standard
requirements, any data configured for Class 1, 2, 3 is also returned in
response to a Class 0 poll request.