state when comms fail. Because it is monitoring DNP frames, this works
for both TCP and UDP connections.
0 (default)
–
no timeout, output never clear
1-65535
–
timeout seconds (maximum approx. 18.2 hours).
Analog
This section is used to set up DNP3 points for Analogue Inputs. The Universal
Hub Base Model has no customer useable analogue inputs, and the
configuration page is reserved for future models.
Point Number:
the field specifies the DNP3 identifier for each Analogue
Input point. The valid range is 0-65535. The Point Number must be
unique for each Analogue Input channel.
Static Variation:
the Static Variation attribute defines the data object
returned in response to a DNP3 static data poll request (i.e. Class 0
request). This attribute must be defined for each analogue input point.
The following table lists the valid types for Analogue point types:
Static Object Type
Group Variation Description
g30v1 32b Analog Input 30
1
32-bit Analogue Input
g30v2 16b Analog Input 30
2
16-bit Analogue Input
g30v3 32b Analog Input
No Flags
30
3
32-bit Analogue Input No Flag
g30v4 16b Analog Input
No Flags
30
4
16-bit Analogue Input No Flag
g30v5 Eng Float Analog
Input
30
5
Single-precision Floating Point
Analogue Input