g32v7 Eng Float
Analog Input with
Time
32
7
Analogue Input Change
Event - single-precision,
floating-point with time
Counter Event Variation:
the field defines the default Variation used to
report Counter Events to the master station. The following table lists the
valid types for Counter point types:
Static Object Type
Group Variation Description
g22v1 32b Counter No
Time
22
1
Counter Change Event - 32-bit
with flag
g22v2 16b Counter No
Time
22
2
Counter Change Event - 16-bit
with flag
g22v5 32b Counter
with Time
22
5
Counter Change Event - 32-bit
with flag and time
g22v6 16b Counter
with Time
22
6
Counter Change Event - 16-bit
with flag and time
Frozen Counter Event Variation:
the field defines the default Variation
used to report Frozen Counter Events to the master station. The following
table lists the valid types for Frozen Counter point types:
Static Object Type
Group Variation Description
g23v1 32b Frozen
Counter No Time
23
1
Frozen Counter Change Event -
32-bit with flag
g23v2 16b Frozen
Counter No Time
23
2
Frozen Counter Change Event -
16-bit with flag
g23v5 32b Frozen
Counter with Time
23
5
Frozen Counter Change Event -
32-bit with flag and time
g23v6 16b Frozen
Counter with Time
23
6
Frozen Counter Change Event -
16-bit with flag and time