Class Max. Events:
if unsolicited responses are enabled, the three Class
Max. Events fields specify the maximum number of events in the
corresponding data class to be allowed before an unsolicited response
is generated. The default is 5 events.
The Universal Hub supports a maximum of 200 events of any type, when
this limit is reached, the oldest events will be overwritten first in the
buffer.
Class Max. Delays:
if unsolicited responses are enabled, the three Class
Max. Delay fields specify the maximum time delay in milliseconds
before an unsolicited response is generated in case an event in the
corresponding class is received. The default value is 5 seconds
(5,000ms).
Input
This section is used to set up DNP3 points for Binary Inputs. The Universal Hub
Base Model has two Digital Inputs and are individually configurable as shown
below:
Point Number:
the field specifies the DNP3 identifier for each binary
Input channel. The valid range is 0-65535. The Point Number must be
unique for each Binary Input Channel. Note that the same Point
Number can also be used by a Binary Output Channel.
Static Variation:
the field defines the data object returned in response
to a DNP3 static data poll request (e.g. Class 0 request). This attribute