17
G
G
A
A
B
600 mm
600 mm
2000 mm
D,E
S
S
F
P
H
C
J
J
L
M
K,N
No flue must penetrate
area within dotted lines
round roof light
LT.AL.W7H.000.020
Dimen-
sions
Terminal location
Minimum
distance
(in mm)
to terminal
(room
sealed)
A
Directly below an opening, air brick,
opening window, etc.
300
B
Above an opening, air brick, opening
window, etc.
300
C
Horizontally to an opening, air brick,
opening window, etc.
300
D
Below a gutter or sanitary pipe work
40
1)
E
Below the eaves
40
1)
F
Below a balcony or carport roof
40
1)
G
Above ground, roof or balcony level
300
H
From vertical drain/soil pipe work
40
1)
J
From an internal or external corner
40
1)
K
From a surface or boundary facing the
terminal
600
2)
L
Vertically from a terminal on same wall
1500
M
Horizontally from a terminal on same
wall
300
N
From a terminal facing the terminal
1200
P
From an opening in a carport (e.g.
door, window) into the building
1200
R
From a vertical structure on the roof
n/a
S
Above an intersection with the roof
n/a
table 02 Minimum distances to terminal
1)
= We advise to use deflectors in case of these small dis-
tances.
2)
= Where the terminal is positioned directly opposite an
opening in the facing wall the min will be 2 m.
n/a = not applicable.
2.5.2 Room sealed flue
See
table 03
for the maximum pipe length of flue ducts and air
supply pipes for this ‘room sealed’ application.
It is not necessary to provide combustion air to the room or
internal space in which the boiler is installed.
24s
28c
35c
39c
Diameter in mm Ø
60/100
80/125
60/100
80/125
60/100
80/125
60/100
80/125
Maximum length ‘L’
allowed [m]
6
29
6
29
7
30
5
25
Eq. Length of 90° elbow
1.4
Eq. Length of 45° elbow
0.65
L
VRS roof
mounted
room sealed
terminal
L
80/125 or 60/100
table 03 Maximum pipe lengths for
fl
ue duct and air supply in
room sealed application