44
Remeha Avanta Plus
Checking values O
2
/CO
2
for natural gas H / L
Boilertype
Fan speed (rpm)
O
2
CO
2
Full load
h3
Part load
L3
% %
24s
ca. 4300
ca. 1300
5.2
± 0.2
8.8
± 0.3
28c
ca. 5500
ca. 1300
5.2
± 0.2
8.8
± 0.3
35c
ca. 6300
ca. 1300
5.2
± 0.2
8.8
± 0.3
39c
ca. 6700
ca. 1300
5.2
± 0.2
8.8
± 0.3
table 10 Checking values O
2
/CO
2
(front panel not
fi
tted)
Checking values O
2
/CO
2
for LPG (propane)
Boilertype
Fan speed (rpm)
O
2
CO
2
Full load
h3
Part load
L3
% %
24s
ca. 4100
ca. 2000
5.1
± 0.2
10.5
± 0.3
28c
ca. 5200
ca. 2000
5.1
± 0.2
10.5
± 0.3
35c
ca. 5800
ca. 2000
5.1
± 0.2
10.5
± 0.3
39c
ca. 6500
ca. 2000
5.1
± 0.2
10.5
± 0.3
table 11 Checking values O
2
/CO
2
(front panel not
fi
tted
z
The O
2
/CO
2
- values
in table 10
are
checking
values. For
setting
values see
table 05 and table 07.
If the flue gas analysis readings are within the values
in table
10
the boiler combustion is OK. However if the readings are
outside the given values, then adjust the gas air ratio control to
the given values,
see table 05 and table 07 in par.2.9.3
.
If the adjustments cannot achieve the mentioned values, the
boiler will require a full service please refer to the maintenance
instructions in
par. 3.2.
-
check the flame via the inspection glass; in full load the
flame should be stable with an even blue colour and in part
load should be stable with an even orange colour.
3.2 Maintenance
To conduct maintenance:
z
Ensure that a service gasket set and new ignition/ionisation
electrode is available before carrying out this procedure.
{
•
Isolate power supply at the fused spur before carrying out
any work on the boiler.