16
Remeha Avanta Plus
2.4.2 Adjusting boiler to other gas-type
The Avanta Plus boilers are suitable for both natural gas and
propane firing. For the Avanta Plus 39c an optional LPG-set is
needed. The boilers are supplied as standard set for natural
gas (H), therefore the following procedure must be carried out
BEFORE the boilers are fired and commissioned for the first
time on propane: Adjust the fan speed (
see Par. 2.9.8
) and
adjust the gas/air ratio (
see Par. 2.9.3
).
2.4.3 Connecting the gas supply
LT.AL.W7H.000.019
•
Before starting any work on the gas supply, turn off the
main isolation valve.
•
Connect the gas supply
to the 22 mm Ø boiler con-
nection.
m
•
Make sure there is no dirt in the gas pipe. Blow through the
pipe before installation or tap well to purge.
•
Make sure that the minimum gas service pressure is high
enough (in full load > 17 mbar).
•
Preferably install a gas filter in the gas pipe to prevent the
gas block from getting dirty.
•
The gas supply must be connected, tested for soundness
and purged by a qualified Engineer and in accordance with
BS6891.
2.5 Flue terminal and air supply connections
The Remeha Avanta Plus is only suitable for room sealed
operation with a standard concentric connection 60/100 mm Ø
or the optional 80/125 mm Ø connection.
Detailed recommendations for air supply and flue terminals are
given in BS 5440.
2.5.1 Flue terminal positions
The flue terminal must be located with care to ensure that the
products of combustion are dispersed properly in all weather
conditions and cause minimum nuisance to the building user
or any adjacent buildings. If the terminal is positioned less
than 2 m above the ground, balcony, or flat roof where access
by persons is possible a suitable guard must be employed.
z
The boiler will produce a water vapour plume during normal
operation.
Positions for the Remeha Avanta
Plus are shown in the figure
and
table 02.
Summary of Contents for Avanta Plus 24s
Page 94: ...30...
Page 95: ...31...
Page 97: ...2 AVANTA PLUS 28 Combi Gas Council No 47 673 02 39 Combi Gas Council No 47 673 04...
Page 100: ...5...
Page 104: ...9...
Page 107: ...12 AVANTA PLUS 24 System Gas Council No 41 288 05...
Page 110: ...15...