30
Regency GF950L-2 Gas Fireplace
installation
Straight Out Horizontal Flueing
Diagram 1
Please note the minimum centerline for
basic install shown above.
HORIZONTAL TERMINATIONS (NON POWER FLUE)
RIGID PIPE 102MM X 168MM
The diagrams below shows examples of horizontal termination arrangements using one 90
o
elbow.
1) A maximum of one 90
o
or two 45
o
elbows is permitted.
2) Minimum distance between elbows is 305mm.
• Maintain clearances to combustibles as listed in the "Clearances" section.
• Horizontal flue must be supported every 0.9m.
• Must use optional rigid pipe adaptor (Part# 510-994) when using Duravent systems.
• A flue guard should be used whenever the termination is lower than the specified minimum or as per local codes.
• Flex system can only be used up to 3m - otherwise rigid flueing must be used.
CL
CL
Min. height
(Rigid)
3
9" (991mm)
center
of hole
Maximum (
)
0.6m
Minimum ( m)
0.3