55M4300CCE00 Rev A
Alarm 2:
Is the %SWL overload limit. If the %SWL is greater than Alarm 2, a
continuous audible alarm will be activated and the red display LED will be ON. The
external red lamp and audible alarm output will be ON.
Alarm 3:
Is the %SWL motion cut limit. If the %SWL is greater than Alarm 3, a
continuous audible alarm will be activated and the red display LED will be ON. The
external red lamp and audible alarm output will be ON. The motion cut output will
be in the stop condition (cut active).
Outside duty radius:
This variable represents a transition distance between the
maximum radius rating and zero capacity, the SWL will decay evenly from the last
point on the chart to zero over the distance set by this variable and applies to all
charts.
Note:
This option is valid only if the chart interpolation (in the system options menu)
is set to "ON".
Outside duty angle:
This variable works in the same way as ‘outside duty radius’ but
is used for charts where the SWL is determined by boom angle and not radius.
Outside duty length:
This variable represents an upper tolerance on the automatic
selection of the relevant load capacity chart for the actual boom length measured by
the system length sensor.
Inside duty length:
This variable represents a lower tolerance on the automatic
selection of the relevant load capacity chart for the actual boom length measured by
the system length sensor.
Number of hoists:
Set to the number of hoists (winches, or hooks) fitted to the crane,
1 for main hoist only or 2 for main and auxiliary hoists.
Duty change >20% SWL:
If set to ON this option allows duty and parts settings to be
changed while a load is suspended, if set to OFF these changes will not be permitted
unless the load is less than 20% of the SWL.
Warning:
This option must be set to
OFF
for European operation.
Sensitivity coefficient (5-50%):
The % value will determine how much variation is
required in order for the load variation to be outside the range of the filter, this
should be left at the default value of 35. The filter will only be functional in the
normal operating mode.
Low frequency Coefficient (10-75):
Adjusts the number of samples the filter will use,
this should be left at default value of 35. The filter will only be functional in the
normal operating mode.