55M4300CCE00 Rev A
Step #4: “Calibration data” Entry
Some or all of this information may be pre-loaded prior to delivery but all entries should
be verified and edited as required before proceeding. Length units in use will be feet or
metres depending on the setting made for ‘calibration units’ in step #3, a reminder is
shown on the bottom line of this display.
Remember to save any changes made.
Please
advise Rayco Wylie of any changes required in this section.
1- In the calibration menu, scroll down to the item "Calibration data:".
2- Press
“
”
to enter this menu.
3-
Scroll to select the item to edit from the list below.
4-
Press
“
”
to highlight the value to edit. Scroll up or down to change the value
then Press
“
”
to confirm.
5-
Any change made must be permanently registered by pressing the
“save”
button.
6-
Press
“
”
at any time to abandon any changes not saved or to exit the menu
when done.
Rope limit Main:
This is the maximum tension that the cable is rated for per fall or
part of line (rope SWL) for the main rope. Note that this value will be monitored
simultaneously with the relevant load table and the hook capacity, the lowest of
these figures will be used as the current SWL for alarm purposes.
Rope limit Aux:
This is the maximum tension that the cable is rated for per fall or
part of line (rope SWL) for the auxiliary rope. Note that this value will be monitored
simultaneously with the relevant load table and the hook capacity, the lowest of
these figures will be used as the current SWL for alarm purposes.
Max parts of line:
This is the maximum number of parts of line that can be rigged on
the crane and applies to all hoists.
Percent per part:
This value allows a reduction in the SWL of the hoist rope when
reeved to more than 1 part, the factor is applied to both main and auxiliary hoists.
For example: entering a value of 1.0 in this field will mean that the maximum load on
1 part will be the rope limit described above, the maximum load on 2 parts will be
two times the rope limit less 1.0%, the maximum load on 3 parts will be three times
the rope limit less 2%, the maximum load on 4 parts will be four times the rope limit
less 3% etc.
Alarm 1:
Is the %SWL approach limit. If the %SWL is greater than Alarm 1, an
intermittent audible alarm will be activated and the yellow display LED will blink. The
external yellow lamp output will be ON.
Note:
%SWL = (Load / Capacity) x 100.