24.5 A1014 Amplifier - Field Checklist
SYMPTOM
POSSIBLE CAUSE
A.
No Gas Flow
1. Modulating valve improperly installed.
B.
Continuous Low Fire (electronics problem).
2. Short circuit or no voltage to the amplifi er.
3. Open circuit in TD114. Remote Temperature Selector circuit or wiring.
4. Short circuit in TS114, Discharge Air Sensor circuit or wiring.
5. Faulty amplifi er.
C.
Continuous Low Fire (electronics ok)
6. Short circuit or open circuit in Modulator Coil.
7. Plunger missing, jammed or improperly installed.
D.
Incorrect Minimum Fire Erratic or Pulsating Flame.
8. Incorrect by-pass metering valve adjustment.
9. Excessive negative burner pressure.
E.
Continuous High Fire (electronics problem).
10. Short circuit in TD114 Remote Temperature Selector circuit or wiring.
11. Open circuit in TS114/TS10765. Discharge or Inlet Air Sensor Circuit or wirin
12. Jumper not connected across amplifi er terminals 2 and 3.
F.
Continuous High Fire (electronics ok).
13. Foreign object holding valve open.
14. Plunger jammed.
G.
Incorrect Maximum Fire.
15. Inlet pressure too low.
16. Incorrect outlet pressure adjustment of Pressure Regulator.
H.
Erratic or Pulsating Flame.
17. Hunting
18. Erratic air patterns or improper TS114 location.
19. Wiring is run next to high voltage switching circuits causing induced voltages
20. Faulty Amplifi er or erratic voltage supply.
I.
Incorrect Discharge Air Temperature
21. Inlet Air Sensor is used.
22. Incorrect Wiring.
23. System out of calibration.
24. Improper TS114 location.
25. Room Override Thermostat circuit closed.
J.
Burned out Transformer.
26. Short circuit in modulator coil.
27. Short circuit between amplifi er and modulator valve.
K.
Discharge Air Temperature too Low when T115 is Opera-
tive
28. Too low an Override Temperature setting.
29. Burner capacity may be insufficient.
Summary of Contents for 4044
Page 2: ......
Page 4: ......
Page 6: ......
Page 8: ......
Page 73: ...SECTION15 VIBRATION ISOLATION 65 of 154 FIGURE 52 Curb Mounted Roof Curb Roof Curb...
Page 109: ...SECTION19 ELECTRICAL 101 of 154...
Page 110: ...4000 SERIES INSTALLATION OPERATION AND SERVICE MANUAL 102 of 154...
Page 111: ...SECTION19 ELECTRICAL 103 of 154...
Page 112: ...4000 SERIES INSTALLATION OPERATION AND SERVICE MANUAL 104 of 154...
Page 113: ...SECTION19 ELECTRICAL 105 of 154...
Page 114: ...4000 SERIES INSTALLATION OPERATION AND SERVICE MANUAL 106 of 154...
Page 115: ...SECTION19 ELECTRICAL 107 of 154...
Page 116: ...4000 SERIES INSTALLATION OPERATION AND SERVICE MANUAL 108 of 154...
Page 117: ...SECTION19 ELECTRICAL 109 of 154...
Page 118: ...4000 SERIES INSTALLATION OPERATION AND SERVICE MANUAL 110 of 154...
Page 119: ...SECTION19 ELECTRICAL 111 of 154...
Page 121: ...SECTION 20 DIRECT FIRED BURNER 113 of 154 FIGURE 71 Midco HMA 2A Burner...
Page 122: ...4000 SERIES INSTALLATION OPERATION AND SERVICE MANUAL 114 of 154...
Page 125: ...SECTION 20 DIRECT FIRED BURNER 117 of 154...
Page 126: ...4000 SERIES INSTALLATION OPERATION AND SERVICE MANUAL 118 of 154...
Page 127: ...SECTION 20 DIRECT FIRED BURNER 119 of 154 20 3 Honeywell UV Flame Detector...
Page 160: ...4000 SERIES INSTALLATION OPERATION AND SERVICE MANUAL 152 of 154...
Page 161: ...SECTION 27 THE RAPID 4000 SERIES WARRANTY 153 of 154...
Page 162: ...4000 SERIES INSTALLATION OPERATION AND SERVICE MANUAL 154 of 154...