Care must be taken to properly select wire size for the input and output of ADG-P
series according to its models; refer to Table 2.1, Table 2.2 and Table 2.3.
Model
Input Current
A/B/C
G
ADG-P & ADG-S (30kW)
60A
16mm
2
16mm
2
ADG-P & ADG-S (50kW)
100A
35mm
2
16mm
2
ADG-P & ADG-S (75kW)
150A
50mm
2
25mm
2
ADG-P & ADG-S (100kW)
200A
95mm
2
50mm
2
*
The wire size is based on the input 380V 3Φ3W + G.
Table 2.1 Input cable size
AWG
AWG
Current Rating
AWG
Current Rating
18
10A
4
100A
16
15A
2
130A
14
25A
1
145A
12
30A
0 (1/0)
170A
10
40A
00 (2/0)
195A
8
55A
000 (3/0)
225A
6
80A
0000 (4/0)
260A
* The ambient temperature should be below 35
℃
, and the temperature rating of conductor insulation
for wires should be at least 60
℃
.
Table 2.2 Current rating of AWG
NOTICE
The tables above give minimum recommended cable size; these recommendations
are for multi core flexible copper cables and are for reference only. The user can
select different cables according to the actual input and output conditions. When
the length of cable is more than 20 meters, the cable gauge should be doubled.