Chapter 5 Function parameter
74
Ch
ap
ter 5
Cleared at the end of down time
2
Hundreds digit
Reserve
Thousands digit
Reserve
5-2-4.
Output terminal group
:
F2.00-F2.19
Code
Parameter name
Setting range
Factory
setting
Cha
nge
F2.00
SPB terminal output
selection
High speed pulse output
0
0
☆
Switching output
1
SPB terminals are programmable multiplex terminal can be used as high-speed pulse output
terminal, it can also be used as open collector output terminal.
As a high-speed pulse output, the maximum frequency of the output pulse is 100kHz, high-
speed pulse output of the correlation function refer to Note F2.06.
F2.01
Switching quantity output function selection (Open collector output
terminal)
0~40
0
☆
F2.02 Relay 1 output function selection (TA1.TB1.TC1)
0~40
2
☆
F2.03 Undefined
F2.04
SPA output function selection (collector open circuit output
terminals)
0~40
1
☆
F2.05 Relay 2 output function selection (TA2.TB2.TC2)
0~40
1
☆
Above 5 function code is used to select five digital output function. Multifunctional output
terminal functions are as follows:
Setting
value
Functions
Description
0
No output
No output action
1
Inverter running
Inverter is in running state, the output frequency (can be zero),
the output ON signal.
2
Fault output (fault down ) When the drive fails and downtime, the output ON signal.
3
Frequency level detection
FDT1 output
Please refer to the function code F7.23, F7.24's instructions.
4
Frequency arrival
Please refer to the description of function code F7.25.
5
Zero-speed running (no
output when shutdown)
Inverter operation and the output frequency is 0, output ON
signal. When the drive is shut down, the signal is OFF.
6
Motor overload pre-alarm
Before the motor overload protection, according to the
overload pre-alarm threshold value judgment, more than the
pre-alarm threshold value output ON signal. Motor overload
parameter settings refer to the function code F8.02 ~ F8.04.
7
Inverter overload pre-
alarm
Before the inverter overload occurs 10s, output ON signal.
Setup counter arrive
8
Setup counter arrive
When the count reaches the set value of E0.08, output ON
signal.
Specifies the count value reaches
9
Specifies the count value
reaches
When the count reaches the set value of E0.09, output ON
signal. Counting Function Reference E0 group
10
Length arrival
When the actual length of the detection of more than E0.05 set
length, output ON signal.
11
PLC cycle is complete
After simple PLC completes one cycle, the output of a pulse
width of 250ms signal.
12
Total running time arrival
Inverter total running time of more than F7.21 F6.07 set time,
the output ON signal.