
Chapter 5 Function parameter
104
Ch
ap
ter 5
cycle(E0.03) × (1 - Triangle wave rise time coefficient(E0.04)), unit: second(s).
E0.05 Set length
0m~65535m
1000m
☆
E0.06 Actual length
0m~65535m
0m
☆
E0.07 Pulse per meter
0.1~6553.5
100.0
☆
The above function codes are used to fixed-length control.
The length information is sampled through the multi-function digital input terminal, the
pulse number sampled by terminal divides the pulse per meter(E0.07), so then the Actual
length(E0.06) can be computed out. When the Actual length is greater than the set length (E0.05),
the multi-functional digital DO will output "Length Arrival" ON signal.
During the fixed-length control, the multifunction DI terminal can be used to reset length
(DI function selects 28), please refer to F1.00 to F1.09 for details.
In some applications, the related input terminal function shall be set to "Length Count
Input"(function 27), when the pulse frequency is higher, DI5 port must be used .
E0.08 Set count value
1~65535
1000
☆
E0.09 Specified count value
1~65535
1000
☆
Set count value DO1
1
Count pulse DI5
Specified continue relay
2
3
4
5
6
7
8
9
Diagram 5-30:
Schematic diagram of the set count value reference and the specified value
The count value needs to be sampled through the multi-function digital input terminal. In
some applications, the related input terminal function shall be set to "Counter Input"(function
25), when the pulse frequency is higher, DI5 port must be used .
When the count value reaches the set count value(E0.08), the multifunction digital DO will
output "Set Count Value Arrival" ON signal, then the counter stops counting.
When the count value reaches the specified count value(E0.09), the multifunction digital
DO will output "Specified Count Value Arrival" ON signal, then the counter continues to count,
and then stop till the set count value.
The figure is the schematic diagram of E0.08 = 8 and E0.09 = 4.
E0.10 Reduction frequency pulse number
0
:
Invalid
;
1~65535
0
☆
E0.11
Reduction frequency
0.00Hz~F0.19(max frequency)
5.00Hz
☆
Applications need to the corresponding input terminals function is set to "counter
input"(function 25), when set count (E0.08) = count (d0.12) + reduction frequency pulse number
(E0.10), the converter automatically slow down to the set reduction frequency (E0.11) run.
Remark: To reset the Count value need to the corresponding input terminals function be set
to "counter reset" (function 26)
5-2-16.
Multi-stage command, simple PLC: E1.00 - E1.51
Code
Parameter name
Setting range
Factory
setting
Change
limits
E1.00 0-stage speed setting 0X
-100.0% to 100.0%
0.0%
☆
E1.01 1-stage speed setting 1X
-100.0% to 100.0%
0.0%
☆
E1.02 2-stage speed setting 2X
-100.0% to 100.0%
0.0%
☆
E1.03 3-stage speed setting 3X
-100.0% to 100.0%
0.0%
☆
E1.04 4-stage speed setting 4X
-100.0% to 100.0%
0.0%
☆
E1.05 5-stage speed setting 5X
-100.0% to 100.0%
0.0%
☆
E1.06 6-stage speed setting 6X
-100.0% to 100.0%
0.0%
☆