Chapter 5 Function parameter
101
Ch
ap
ter 5
works under the speed control mode, the other inverter as the auxiliary unit that works under the
torque control mode, the Actual output torque of the master unit is used as the torque command of
the auxiliary, the torque of the auxiliary needs quickly follow the master unit, so the torque control
ac/deceleration time of the auxiliary unit shall be set to 0.00s.
FA.05
Torque control forward
maximum frequency
0.00Hz~maximum frequency (F0.19)
50.00H
z
☆
FA.06
Torque control backward
maximum frequency
0.00Hz~ maximum frequency (F0.19)
50.00H
z
☆
Used to set the maximum operating frequency of inverter forward or reverse running under
the torque control mode
Under the torque control mode, if the load torque is less than the motor output torque, the
motor speed will continue to rise, in order to prevent "Runaway" and other accidents of
mechanical systems, it is necessary to limit the maximum speed of motor under the torque control
mode.
FA.07
Torque filter time
0.00s~10.00s
0
☆
5-2-13.
Control optimization parameters: Fb.00-Fb.09
Code
Parameter name
Setting range
Factory
setting
Change
limits
Fb.00
Fast current limiting
manner
Disable
0
1
☆
enable
1
Enable Quick Current Limiting function, which can minimize the overcurrent fault of
inverter , and ensure the uninterrupted operation of inverter. If the drive is in the state of fast
current limiting for a long period of time , the inverter may be damaged by overheating and others,
this case is not allowed, so the inverter will alarm fault with fault ID Err.40, it indicates that the
inverter exists overload and needs to be shut down.
Fb.01 Undervoltage point setting 50.0%~140.0%
100.0%
☆
Used to set the voltage value of inverter undervoltage fault with fault ID Err.09 , the different
voltage levels of inverter 100.0% corresponds to the different voltage points are as follows:
Single-phase 220V or three-phase 220V: 200V three-phase 380V: 350V
Three-phase 480V: 450V three-phase 690V: 650V
Fb.02 Overvoltage point setting 200.0V~2500.0V
-
★
The setting over voltage point of the software has no influence on the setting over voltage
point of the hardware. The value of the voltage set to the frequency inverter, different voltage level
„s factory defaults are as following:
Voltage level
over voltage point factory defaults
Single phase 220V
400.0V
Three phase 220V
400.0V
Three phase 380V
810.0V
Three phase 480V
890.0V
Three phase 690V
1300.0V
Remark: Meanwhile, the factory defaults are the upper limit value of over voltage protection
in frequency inverter. Only when Fb.02 setting value is smaller than all voltage factory defaults,
the new parameter setting takes effect. If it is higher than factory defaults, factory defaults will be
the standard value.
Fb.03
Deadband compensation mode
selection
no compensation
0
1
☆
compensation mode 1
1
compensation mode 2
2
Generally do not need to modify this parameter, only when the special requirements to the
output voltage waveform quality is required or when the motor oscillation and other abnormal
happen, you need to try to switch to select a different mode of compensation.The compensation
mode 2 for high-power is recommended.