Chapter 5 Function parameter
44
Ch
ap
ter 5
momentary power cut
deceleration
283.
F8.28
Recovery voltage judgment time
of momentary power cut
0.00s to 100.00s
0
☆
284.
F8.29
Judgment voltage of momentary
power cut action
50.0% to 100.0% (standard
bus voltage)
10%
☆
285.
F8.30 Load drop protection selection
0: Invalid
1: Valid
1.0s
☆
286.
F8.31 load drop detection level
0.0 to 100.0
%
0
☆
287.
F8.32 Load drop detection time
0.0 to 60.0s
110
☆
288.
F8.33 motor temperature sensor type
0: Invalid;1
:
PT100 detect
90
☆
289.
F8.34 motor over heat protection value 0
~
200
110
☆
290.
F8.35 motor over heat alma value
0
~
200
90
☆
5-1-11.
F9 Group - Communication parameter
No. Code
Parameter name
Setting range
Factory
setting
Chan
ge
291.
F9.00 Baud rate
Units digit:MODBUS
Tens digit:Profibus-DP
Hundreds digit:Reserve
Thousands digit:CAN bus baudrate
6005
☆
292.
F9.01 Data format
0: no parity (8-N-2) 2: odd parity (8-O-1)
1: even parity (8-E-1); 3: no parity (8-N-1)
0
☆
293.
F9.02 This unit address
1-250, 0 for broadcast address
1
☆
294.
F9.03 Response delay
0ms-20ms
2ms
☆
295.
F9.04
Communication
timeout time
0.0
(
Invalid
);
0.1~60.0s
0.0
☆
296.
F9.05 Data protocol selection
Units digit: MODBUS
0: non-standard MODBUS protocol
1: standard MODBUS protocol
Tens digit: Profibus-DP
0: PP01 format;
1: PP02 format
2: PP03 format;
3: PP05 format
30
☆
297.
F9.06 Current resolution
0: 0.01A
1: 0.1A
0
☆
298.
F9.07 Baud rate
Units digit:MODBUS
Tens digit:Profibus-DP
Hundreds digit:Reserve
Thousands digit:CAN bus baudrate
6005
☆
5-1-12.
FA Group - Torque control parameters
No. Code
Parameter name
Setting range
Factory
setting
Chan
ge