UDACT-9100 Dialer Installation and Operation Instructions
21
CommandMenu/Dialer-Config/Report Options
1.Alarm priority
[X] Account 1->Def
[ ] Account 2
Use this function to set
the account priority for
reporting alarms. If the
priority is set for
account#1 then the dialer
will try account#1 first for
reporting.
CommandMenu/Dialer-Config/Report Options
2.Trouble priority
[X] Account 1->Def
[ ] Account 2
Use this function to set
the account priority for
reporting trouble. If the
priority is set for
account#1 then the dialer
will try account#1 first for
reporting.
CommandMenu/Dialer-Config/Report Options
3.Supervisory priority
[X] Account 1->Def
[ ] Account 2
Use this function to set
the account priority for
reporting supervisory
troubles. If the priority is
set for account#1 then the
dialer will try account#1
first for reporting.
Command Menu/Dialer-Config/Report Options
4.Ignore Supervisory
[ ] ENABLE
[X] DISABLE->Default
If this function is enabled,
the UDACT-9100 will
bypass all supervisory
event reporting.
Command Menu/Dialer-Config/Report Options
5.Protocol type
[ ] Level 0
[X] Level 1
[ ] Level 2
[ ] Level 1-G
Change this function as
required for appropriate
fire alarm panel. Level 1
is the PFC-5000. Level 2
is the PFC-9000 and
Level 0 and 1-G are not
used.
Command Menu/Dialer-Config/Report Options
6.Dialer operation mode
[X](U)DACT ->Default
[ ] DACT
Use this function to select
the functionality of the
dialer. In DACT mode
only common trouble/
alarm/supervisory are
reported, while in UDACT
mode all zone point
information is reported
Command Menu/Dialer-Config/Report Options
7.Checksum Bits
[X] 8 Bit->Default
[ ] 16 Bits
For PFC-5000 and
PFC-9000, choose 8 Bits.
16 Bits is not used.
A l a r m P r i o r i t y :
[ X ] A c c o u n t 1
T r o u b l e P r i o r i t y :
[ X ] A c c o u n t 1
S U P V P r i o r i t y
[ X ] A c c o u n t 1
Ignore Supervisory
[X] Disable
Protocol:
[X] Level 1
D i a l e r O p e r . M o d e :
[ X ] ( U ) D A C T
Checksum Bits:
[X] 8 Bits