Configuration & LCD Operation
12
1. View Event Log
Pressing the “INFO” key provides more information about the displayed event. The illustration below provides an
example of how the “INFO” key works.
There are a maximum of 500 recent events saved in the event log. If the number of events goes beyond 500, all
new incoming events will be ignored.
2. Clear Event Log (Command-Menu)
Select the type of log to view. Press the
“ENTER” key. The system will then
show the log chosen.
Use this function to select the log to view. Either the
local or remote log. The remote log contains all
events associated with the fire alarm panel. The local
log contains all events associated with the UDACT-
9100. Each log can hold up to 500 events.
Select the type of log to clear. Press the
“ENTER” key. The system will then
confirm before clearing logs.
Press the “ENTER” key to confirm or the
“CANCEL” key to cancel the operation.
Use this function to clear remote logs, local logs, or
both. The remote log contains all events associated
with the fire alarm panel. The local log contains all
events associated with the UDACT-9100 at the panel.
Each log can hold up to 500 events.
-View Event Logs-
1 Remote Log
2 Local Log
of
-Clear Log-
1 Remote Log
2 Local Log
3 All Logs
C l e a r a l l t h e
s e l e c t e d l o g ( s ) ? Y
L o g ( s ) c l e a r e d