UDACT-9100 Dialer Installation and Operation Instructions

15

4. Config Info (Command-Menu)

5. Version Info

 

The first line shows the model number and panel type and the second line shows the software version number. The 
version of the software is read as Major.Minor.Revision. The display will remain for 10 seconds.

Press down arrow key to see more
information.

Configuration type will show how the panel was configured.  
“Factory default” means the panel has not been configured, 
it is as it came from the factory.  “Front Panel” means it was 
configured at the panel. “Serial Port” means the 
configuration was done from a computer through the serial 
port. “Modem” means the configuration was completed 
remotely through a modem.

If you upload a job configuration to the panel using the PC 
configuration utility, the job name will appear on this 
screen. The job name can be up to a maximum of 20 
characters.

Press down arrow key for further 
info

If you upload a job configuration to the panel using the PC 
configuration utility, the technician’s name (ID) will appear 
on this screen. The technician ID can be up to a maximum 
of 10 characters.

Press down arrow key for further 
info

Configuration date and time will appear for all means of 
configuration, thus revealing date and time configuration 
was last changed.

This specifies the configuration tool version. It will display 
0.0.0.0 if no PC configurator has been used.

C o n f i g u r a t i o n   t y p e :

F a c t o r y   d e f a u l t

J o b   N a m e :

N o   j o b   l o a d e d

T e c h n i c i a n   I D :

U n k n o w n

C f g .   D a t e   a n d   T i m e :

h h : m m   d a y   y e a r : m m : d d

C f g .   T o o l   S / W   V e r s . :

V e r s i o n : x . x . x . x

   S/UDACT-9100

   Version 1.0.1

firealarmresources.com

Summary of Contents for UDACT-9100

Page 1: ...by the manufacturer UDACT 9100 Digital Alarm Communicator Transmitter INSTALLATION and OPERATION MANUAL 2008 by Potter Electric Signal Company Novmber 2008 LT 888POT Rev 2 1 5 8 0 ENTER MENU CANCEL INFO 6 2 ABC 3 DEF 4 GHI JKL MNO 7 PRS TUV 9 WXY QZ RS 485 COMMON TROUBLE CPU FAIL LINE 1 LINE 2 POWER ON firealarmresources com ...

Page 2: ...firealarmresources com ...

Page 3: ...Setup 9 CONFIGURATION VIA ON BOARD KEYPAD 9 CONFIGURATION VIA a UIMA AND COMPUTER LOCAL 9 CONFIGURATION VIA MODEM AND COMPUTER REMOTE 9 Configuration LCD Operation 10 Entering the Passcode 11 Command Menu 11 1 View Event Log 12 2 Clear Event Log Command Menu 12 3 Test Dialer Command Menu 13 4 Config Info Command Menu 15 5 Version Info 15 6 Set Time Command Menu 16 7 Set Password Command Menu 17 8 ...

Page 4: ...firealarmresources com ...

Page 5: ...mong other information a product identifier in the format US 1M8AL02BUDACT300A If requested this number must be provided to the telephone company This equipment is capable of seizing the line This capability is provided in the hardware The Ringer Equivalence Number REN assigned to each terminal device provides an indication of the maximum number of devices that may be connected to a telephone line...

Page 6: ... problem they may temporarily discontinue service When practical they will notify you in advance of this disconnection If advance notice is not feasible you will be notified as soon as possible When you are notified you will be given the opportunity to correct the problem and informed of your right to file a complaint with the FCC Contact your telephone company if you have any questions about your...

Page 7: ...o a DACR using Ademco Contact ID or SIA DCS reporting protocols 300 baud or 110 baud rate The UDACT 9100 has the ability of disconnecting the incoming and outgoing calls and capturing the line for transmission to the DACR Provides telephone line monitoring and reports status via LED indication on board yellow for trouble and red for dialing out User configurable locally by on board keypad and a CF...

Page 8: ...stalled in and is described in the appropriate FACP Installation Manual Figure 1 below shows the mechanical installation for an PFC 5002 and PFC 5004 FACP Figure 1 UDACT 9100 Mechanical Installation Notes 1 Front plate is not shown 2 Reserved for PR 5000andUDACT9100 3 Other circuit adder modules may be ZA 9008 Detection Circuit Adder Module IDC 9004 Signal Circuit Adder Module ARM 9008 Relay Circu...

Page 9: ...pushbutton and LEDs Table 1 following provides a description of the user items on the UDACT 9100 Figure 2 UDACT 9100 Board Layout 1 5 8 0 ENTER MENU CANCEL INFO 6 2 ABC 3 DEF 4 GHI JKL MNO 7 PRS TUV 9 WXY QZ P1 RS 485 COMMON TROUBLE CPU FAIL LINE 1 LINE 2 POWER ON UDACT Prot 1 Idle 18 01 MON 2006 04 05 T R RES T R RES T R C O T R C O Line 1 Relay Line 1 Relay Line 2 Line 2 I2 I3 U18 UR1 CONTRAST A...

Page 10: ...s active Common Trouble Steady amber for any troubles on the Fire Alarm panel or UDACT 9100 CPU Fail Steady amber for any on board CPU trouble Telephone Line 1 Telephone status indicator LED Red when the line is in use Amber when there is a line trouble Telephone Line 2 Telephone status indicator LED Red when the line is in use Amber when there is a line trouble Power ON Green LED is ON steady whe...

Page 11: ...in Figure 3 below The UDACT 9100 terminals are located on the top left hand corner of the board If using a cellular or wireless service use the Line 2 interface connection only Figure 3 Telephone Line Wiring Diagram Note Most Authorities Having Jurisdiction AHJ do not allow the connection of premise telephones see specifications for more information UDACT 9100 firealarmresources com ...

Page 12: ...eshold a Communication Trouble with ID 485 will be reported during the 24 hour periodic test While working in the DACT mode UDACT 9100 scans the common relay connections from the FACP including Common Alarm Common Supervisory and Common Trouble relays and reports the common status only The UDACT 9100 is capable of reporting multiple events to a single account number within a single call session Fo...

Page 13: ...n cable connector of UIMA is connected to P2 on UDACT 9100 board A serial cable or USB cable is needed to connect the UIMA to the computer 2 Place a jumper at JW2 on the UDACT 9100 board to allow the configuration a trouble is generated and reported to the receiver DACR 3 Start the Potter Software MSW 012 on the computer to configure the UDACT 9100 Follow the instructions of MSW 012 menu to comple...

Page 14: ...over the 3 standoffs as shown in Figure 2 In order to configure the UDACT 9100 place a jumper on JW2 remove once configuration is complete otherwise there will be a trouble message To access configuration mode press the Menu button on the front panel display The CFG LCD will display the Main Menu The keypad on the UDACT 9100 board and the CFG LCD is shown together in Figure 4 below Figure 4 UDACT ...

Page 15: ...ommand menu is pictured below The first line of the LCD will always show Command Menu and the second line displays the different selections Use the UP and DOWN keys to move through the menu and press the ENTER key to make a selection To exit from the main command menu press CANCEL or select the Exit menu option and then press the ENTER key After you select a feature item by pressing the ENTER key ...

Page 16: ...ains all events associated with the fire alarm panel The local log contains all events associated with the UDACT 9100 Each log can hold up to 500 events Select the type of log to clear Press the ENTER key The system will then confirm before clearing logs Press the ENTER key to confirm or the CANCEL key to cancel the operation Use this function to clear remote logs local logs or both The remote log...

Page 17: ...operation Press Enter to reset the dialer Press Cancel to exit this menu The dialer is checking the line for voltage This message automatically displays when Manual Test is selected No DC line voltage The line is dead or no phone line is connected or the phone line operates at abnormal voltage The dialer is waiting for a dial tone This message may indicate a noisy telephone line The dial tone was ...

Page 18: ...ilable Sending events to the receiver The dialer is waiting for the Kissoff tone The Kissoff tone indicates that the receiver has received the event reports No Kissoff means dialer did not detect Kissoff tone The line passed the test everything is OK Failed No Acktone Reporting Event Now Waiting for Kissoff No Kissoff Passed Manual test firealarmresources com ...

Page 19: ...ugh a modem If you upload a job configuration to the panel using the PC configuration utility the job name will appear on this screen The job name can be up to a maximum of 20 characters Press down arrow key for further info If you upload a job configuration to the panel using the PC configuration utility the technician s name ID will appear on this screen The technician ID can be up to a maximum ...

Page 20: ...anges and the CANCEL key to ignore the changes Note time is in 24hr format Command Menu Time Clock 3 Compensation Once the compensation value is entered the display will be Compensation value can range from 15 to 15 seconds Use the up down arrow keys to select daily compensation value and press ENTER For a fast clock adjust negatively For a slow clock adjust positively For example for a clock whic...

Page 21: ...code The minimum number of digits is 4 and the maximum number is 10 ONLY numeric digits are allowed Command Menu Default Config Press UP and DOWN to select between Y N if ENTER is pressed the default configuration is restored Use this function to load the default configuration in the panel Warning By loading default configuration all the previously programmed configuration is lost permanently Ente...

Page 22: ...to 9 and hexadecimal digits A to F The SIA protocol only allows digits 0 to 9 To enter hexadecimal digits press the INFO button The letter A will appear To scroll through the rest of the letters press INFO repeatedly Press key to move the cursor to the right or press key to move it to the left Command Menu Dialer Config Account Info 2 Account 1 Telephone Number 101 Default Use this function to set...

Page 23: ...u Dialer Config Account Info 4 Account 2 Identification 654321 Default Same as Account 1 Command Menu Dialer Config Account Info 5 Account 2 Telephone Number 101 Default Same as Account 1 Command Menu Dialer Config Account Info 6 Account 2 Reporting Format X Contact ID Default SIA 300 Baud SIA 110 Baud Same as Account 1 A C C N T 1 F o r m a t X C o n t a c t I D Account 2 ID 654321 Account 2 Teln...

Page 24: ... tone detection should be disabled Command Menu Dialer Config Telephone Line 5 Number of retries 06 Default Set the number of retries for both line 1 and line 2 This function lets the dialer retry on either line if it is busy or not available If the retry count expires the panel reports a line trouble 1 L i n e 1 D i a l t y p e 2 L i n e 2 D i a l t y p e 3 L i n e 1 D i a l t o n e 4 L i n e 2 D...

Page 25: ... 4 Ignore Supervisory ENABLE X DISABLE Default If this function is enabled the UDACT 9100 will bypass all supervisory event reporting Command Menu Dialer Config Report Options 5 Protocol type Level 0 X Level 1 Level 2 Level 1 G Change this function as required for appropriate fire alarm panel Level 1 is the PFC 5000 Level 2 is the PFC 9000 and Level 0 and 1 G are not used Command Menu Dialer Confi...

Page 26: ...ault as is at 0 Command Menu Dialer Config Time Parameter 3 Auto test time 00 30 Default Use this function to set the time for auto test This test has to be performed once a day to send the test report to the monitoring station The time is in 24hr format which means 00 30 is 30 minutes after midnight Please avoid the following Test Times 00 00 01 55 02 00 and 03 00 1 A C L o s s D e l a y 2 C e l ...

Page 27: ...warning message appears Warning The dialer cannot report any event to the monitoring station if it is disabled Command Menu Dialer Config Enable Disable Disabled 1 2 3 4 X 5 Default 6 7 8 Use this menu item to select the number of rings on which the panel s modem will answer The default number of rings is five The maximum number of rings you can define is eight If you select the Disabled option th...

Page 28: ...st New event 1 601 00 000 Event Description Event Family Qualifier Code Group Contact Zone Fire Alarm Alarm New event 1 110 00 NNN Zone Fire Alarm restored Alarm Restore 3 110 00 NNN Zone Trouble detected Trouble New event 1 300 00 NNN Zone Trouble restored Trouble Restore 3 300 00 NNN Zone Supervisory condition Supervisory New event 1 200 00 NNN Zone Supervisory restored Supervisory Restore 3 200...

Page 29: ...t Off normal Test New event RY 000 Manually initiated dialer test Test New event RX 000 Event Description Event Family Qualifier SIA Event Code Parameter Zone Fire Alarm Alarm New event FA NNN Zone Fire Alarm restored Alarm Restore FH NNN Zone Trouble detected Trouble New event FT NNN Zone Trouble restored Trouble Restore FJ NNN Zone Supervisory condition Supervisory New event FS NNN Zone Supervis...

Page 30: ...e Receiver ULC ULI Approved SIA DCS and Ademco Contact ID SurGard SLR Single Line Receiver ULC ULI Approved SIA DCS and Ademco Contact ID Osborne Hoffman Quickalert II Receiver ULI Approved SIA DCS and Ademco Contact ID Osborne Hoffman OH 2000 Receiver ULI Approved SIA DCS and Ademco Contact ID Silent Knight Model 9500 Receiver ULI Approved SIA DCS and Ademco Contact ID Radionics Model D6500 Recei...

Page 31: ...ing between the Communicator and the FACP Transmits Zoned Alarm Supervisory and Trouble status to a Central Monitoring Station using either Ademco Contact ID or SIA DCS Protocols User configurable locally or remotely Configuration is passcode protected Current Consumption Standby 40 mA Alarm 60 mA Battery Calculations UDACT 9100 The UDACT 9100 Battery Calculations are performed as part of the calc...

Page 32: ...onsible to repair or replace equipment which has been repaired by others abused improperly installed altered or otherwise misused or damaged in any way Unless previously contracted by Potter Potter will assume no responsibility for determining the defective or operative status at the point of installation and will accept no liability beyond the repair or replacement of the product at our factory a...

Page 33: ...ceiving station including area code ____________________ Reporting Format Contact ID SIA _________________________________________________________________________________________ Account 2 Identification max 6 digits _ _ _ _ _ _ Account 2 Telephone number including area code __________________________ Telephone number of receiving station including area code ____________________ Reporting Format C...

Page 34: ...Notes firealarmresources com ...

Page 35: ...firealarmresources com ...

Page 36: ...Potter Electric Signal Company 2081 Craig Road St Louis Missouri USA 63146 4161 firealarmresources com ...

Reviews: