Connections and Settings
6
Table 1: Cable Connectors and Miscellaneous
The following table lists all the LEDs located on the UDACT-9100 board and states the function of each LED.
Table 2: UDACT-9100 List of LEDs and their Functions
Cable Connector
Function
P1
Ribbon Cable for connecting to Potter Fire Alarm Control Panel (FACP)
P2
RS-232C/RS-485 Connection for computer configuration.
U18
Connector for CFG-LCD Configuration Tool
Lamp Tes
t button
Press and hold this button to test all the UDACT-9100 LEDs and LCD display
UR1 Potentiomete
r
This potentiometer is for adjustment of the CFG-LCD LCD contrast.
LEDs
FUNCTION
Relay Line 1
Located below Line 1 terminal block. When Line 1 relay is energized, this green
LED will illuminate
Relay Line 2
Located below Line 2 terminal block. When Line 2 relay is energized, this green
LED will illuminate.
RS-485
Status LED for communication, will flash when RS-485 communication is active.
Common Trouble
Steady amber for any troubles on the Fire Alarm panel or UDACT-9100.
CPU Fail
Steady amber for any on board CPU trouble.
Telephone Line 1
Telephone status indicator LED; Red when the line is in use, Amber when there is
a line trouble.
Telephone Line 2
Telephone status indicator LED; Red when the line is in use, Amber when there is
a line trouble.
Power ON
Green LED is ON steady when power is supplied to the board.
The following table lists the user jumpers available on the UDACT-9100 and their functions.
Table 3: UDACT-9100 List of Jumpers for Operation and Configuration
JUMPER NUMBER
JUMPER FUNCTIONS
JW1
Normally open. Place jumper here and power down the UDACT-9100 by
disconnecting P1 or power down the fire alarm panel (AC and Batteries), then power
back to revert to default passcode. After reset, remove the jumper. Leave normally
open.
JW2
Normally open to BLOCK remote configuration via modem, PC with a UIMA converter
module or using the LCD and keypad at the UDACT-9100. Place jumper here to
ALLOW any type of configuration. Remove jumper once configuration is complete.