ComPak
®
Series - Installation, Operation and Maintenance |
55
ComPak
®
Series IOM
DEHUMIDIFICATION STAGE 2 OFFSET (IN DEGREES OF DEW POINT) - 0 TO 9.9°F (4.0°F).
Determines how far humidity of the space has to rise above the set points before the unit will request 2 stages
of dehumidification on the network. This parameter is normally the same in all units on the network. Making this
parameter smaller will bring on the second stage of dehumidification sooner.
ENABLE NETWORK CONTROL - YES OR NO
Determines whether the unit will participate in the master/slave environment. Setting this parameter to NO will
cause the unit to act like a standard CPCS-PCP single unit. The unit will never become the master on the network
and will not listen to the demands broadcast by the master on the network. Although units with this parameter
set to NO do not participate in the master/slave environment, they are still accessible through the network
control panel. Like the LOCAL pool water temperature setting, this parameter, when set to NO, requires this unit
to be displayed on the control panel before changing any of the set points. The other screens for Pool Water
Temperature Control, Staged Dehumidification, and Stage 2 Offset are not available when this parameter is set
to NO.
CHANGING SET POINTS
Each unit on the network maintains two groups of set points, network and local. If a unit has the Enable
Network Control parameter set to YES and the Water Temperature Control parameter set to NETWORK, it will
control to the network set points. Set points changed when the remote interface unit is displaying this unit will be
changed in every unit on the network with the same NETWORK and Water Temperature Control parameters.
Units that are configured for Network
Control and LOCAL water temperature control will control using local water temperature set point, the network
air temperature and relative humidity set points. When the air temperature and relative humidity set points are
changed when the remote interface unit is displaying the unit, they will be changed in all units configured for
Network control. The water temperature set point will only be changed in the unit currently being displayed by
the remote interface unit. Units that are not configured for Network Control will use all local set points. Therefore
any set points changed while the remote interface unit is displaying this unit will only be changed in this unit.