www.poolpak.com | 800-959-7725
24
| ComPak
®
Series - Installation, Operation and Maintenance
Hot Water Coil Capacities
Table 3-6. Hot Water Coil Capacities
VERTICAL (AWV, HCDV) MODELS 1 ROW HOT WATER COIL
MODEL
FLOW RATE RANGE (GPM)
HEATING CAPACITY RANGE (MBH)
MIN
MAX
MIN
MAX
0550
5
15
35
56
0800
5
15
44
69
1200
5
15
48
75
1400
10
25
73
109
1800
10
25
82
115
2600
15
35
108
166
3500
20
40
165
248
4000
20
40
165
248
HORIZONTAL (AWH, HCDH) MODELS 1 ROW HOT WATER COIL
MODEL
FLOW RATE RANGE (GPM)
HEATING CAPACITY RANGE (MBH)
MIN
MAX
MIN
MAX
0550
5
15
33
54
0800
5
15
43
66
1200
5
15
48
75
1400
10
25
71
105
1800
10
25
80
111
2600
15
35
104
161
3500
20
40
147
203
4000
20
40
158
209
HORIZONTAL (AWH, HCDH) MODELS 2 ROW HOT WATER COIL
MODEL
FLOW RATE RANGE (GPM)
HEATING CAPACITY RANGE (MBH)
MIN
MAX
MIN
MAX
0550
15
25
54
84
0800
15
25
76
108
1200
15
25
87
123
1400
20
35
115
168
1800
20
35
134
180
2600
30
50
167
258
3500
35
55
237
326
4000
35
55
260
340
Coils add 0.1”WC to ESP
Entering Air Temperature - 80°F
Entering Water Temperature - 180°F
Max. Working Pressure - 125 psi
Capacity is a function of Return Airflow and is independent of Supply Airflow
NOTE